View larger
1SDA100488R1
100488
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2354 |
| Environmental Product Declaration - EPD | 9AKK108468A1899 |
| 9AKK108468A9748 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 59.6 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 2ecca021-148a-4716-86ab-b99f951b75d5 Italy |
| Simplified SCIP | e97e1c54-3fd2-4dba-b58b-10765efb9dca Germany |
| 779c8836-e49a-47b7-ae92-5f7afcb8fb86 Estonia | |
| 480c1f22-7dda-4982-9c64-f7628b37aaee Hungary | |
| c8b9810c-5f31-4387-8ddc-b4ec0173fde2 Portugal | |
| cf386a14-374f-42ad-929c-fb3719a542a7 Bulgaria | |
| d8bf7bcd-fd8d-447b-a707-2a4750c185b8 Denmark | |
| 111d3af6-49ad-4f6d-9ab8-449dc83f5f82 Poland | |
| 2cbe260e-6c81-43ee-bfc0-db1c2f3245a2 Sweden | |
| cffca834-1be8-4516-83fa-27c34d07a1cc Poland | |
| 6d780ea6-2e76-4cf4-8fe1-79e6cfd2572e Sweden | |
| 9927ff62-61d4-4f18-9bde-07be414dff58 France | |
| 8db894b9-d570-4117-8058-e768c01f7846 Germany | |
| d4de05d7-ab72-407e-b5b6-f492c97039f5 Norway | |
| 9e74179a-3af8-4ec1-b96b-ad8d0d658704 Finland | |
| ce906cf0-57e2-400b-a86d-f0f53d67b1a3 Croatia | |
| 43826555-7f65-4c91-ae35-7c4b290a2db3 Belgium | |
| ff52ef10-da7a-4c61-9ccc-70c2b306eab0 Czech Republic | |
| 1326ec2e-a3c1-4089-b614-339f11ed488e Germany | |
| 5945a817-6309-4f68-977f-4dd711fbe2c4 Germany | |
| 0d632569-a31a-46de-a6df-48ea923403f1 Hungary | |
| 14a702a9-501d-408b-8b63-ae812556e8ac Spain | |
| 5450d5a3-3583-4039-8d67-e7fe70eb424b France | |
| 4827ea14-729a-4315-be49-b410e028f343 Germany | |
| cb262217-19a6-47f7-9923-736d2ce91877 Poland | |
| 4917600e-3ab4-4b2f-9fa0-4cd2a057fa74 Belgium | |
| b2902597-6767-4034-9331-715d116f31e6 Netherlands | |
| 85204bfe-fd74-46fa-aa37-9e2e9a33f2c5 Greece | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT5HE325AEFF000XXX |
| E-Number (Norway) | 4380299 |
| EAN | 8056221005654 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 140 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 4.82 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 250 mm |
| Package Level 1 Height | 245 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 5.308 kg |
| Package Level 1 EAN | 8056221005654 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1115 |
| 1SDH002065A1131 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 7000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | 8 W |
| Rated Current (In) | 250 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 40 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 5 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 40 kA | |
| Rated Uninterrupted Current (Iu) | 400 A |
| Release | Ekip Dip LS/I |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC60947-2 |
| Sub-type | XT5 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2824 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002011A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002011A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 250 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 100.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 250 A |
| Adjustment range undelayed short-circuit release (EF007131) | 250 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |