View larger
1SDA100399R1
100399
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2354 |
| Environmental Product Declaration - EPD | 9AKK108468A1899 |
| 9AKK108468A9748 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 59.6 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 5dc383d6-321e-4cef-87b5-52a62789885a Italy |
| Simplified SCIP | 570406de-9e6d-4400-acde-be5514be483c Czech Republic |
| b73dd563-38b3-42e8-931e-5c4ee212ef23 Poland | |
| 563ddd4d-1428-42aa-a727-b91382075eeb Germany | |
| 0bdaa1cf-9d16-4f60-ba8d-380b414e206f Denmark | |
| 3e285e38-9125-4b10-b822-69e327bca736 Croatia | |
| 928a1f96-81db-4329-9140-3d91f7625e03 Belgium | |
| 2fae6338-a4d5-49e0-971d-242006d7a522 Germany | |
| d7a5f707-9b45-41c4-8b54-413a7d97a40c Netherlands | |
| 846907d4-14c0-457f-9588-85177cacf353 Germany | |
| 8ba0989e-00a8-4fe0-a636-ac18ae8cf85d Poland | |
| d738ad9d-d6f0-4223-b930-f05a3286ab5b Greece | |
| fdf1a86b-2f0f-4050-bea5-d49334aaf511 Estonia | |
| 09caba6c-bc4f-42dd-8bc6-e46bad8386cd Poland | |
| 94c1a01d-3dac-40f7-a97f-45f63b24618a Sweden | |
| 5fcd6331-30f3-4716-b240-bcf0e588d4b4 Portugal | |
| 35814a86-2dbb-438f-aa56-b67cc4b5f3b5 Bulgaria | |
| afe27379-e111-4171-a677-836d60ef4c06 Finland | |
| 3ce5cb9d-df95-4871-9473-524dd718c100 Germany | |
| 9ae29177-f654-4b53-b507-2cbbe058ded4 Norway | |
| b656b5eb-c9f2-4683-aecd-58789fa71bc9 Sweden | |
| 0fe2fa2e-ddf3-42e1-8d6f-f20ad7b0f41c France | |
| 91555663-675e-4bf4-8adf-9edfd76dd0e9 Hungary | |
| 04359513-a5ed-443a-beaf-0433b363eb67 Belgium | |
| 24b575dd-a988-4c08-b304-73605d7327f7 Spain | |
| 2b5c02e7-bf4f-4564-8181-c6b32a633505 France | |
| 580bb710-3011-4a07-95a4-4e2e7779e745 Germany | |
| 886ae88f-c7f0-4b77-8f85-597510d41bbd Hungary | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT5NE432AFFF000XXX |
| E-Number (Finland) | 3641324 |
| E-Number (Norway) | 4380407 |
| EAN | 8056221004763 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 186 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 6.4 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 250 mm |
| Package Level 1 Height | 245 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 6.888 kg |
| Package Level 1 EAN | 8056221004763 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1183 |
| 1SDH002065A1131 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 7000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 4P |
| Order Multiple | 1 piece |
| Power Loss | 11.6 W |
| Rated Current (In) | 320 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 5 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Uninterrupted Current (Iu) | 400 A |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC60947-2 |
| Sub-type | XT5 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2824 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002011A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002011A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 320 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 128.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 320 A |
| Adjustment range undelayed short-circuit release (EF007131) | 320 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |