View larger
1SDA100396R1
100396
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2354 |
| Environmental Product Declaration - EPD | 9AKK108468A1899 |
| 9AKK108468A9748 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 59.6 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | c51bcf4d-6889-423e-80e7-c8b63cb9e5bb Italy |
| Simplified SCIP | 24878c87-21ad-4955-8a40-16e709df5538 Germany |
| bb0d7387-73a4-4cf3-bb40-5e6323984e51 Germany | |
| 6a1b2580-96e4-4378-a8b4-c508ad328084 Germany | |
| 9dcdc12b-2943-4ad5-9bd4-9295589bb604 France | |
| 8121927a-fa90-4141-8317-5c9234d8ddb2 Netherlands | |
| 84f5995a-e892-40af-b5e3-5d03b5380763 Spain | |
| 523bc9b9-ccc7-46b1-83b3-310bc9d4914a Netherlands | |
| 6c3b81f8-0824-4ea5-8548-b87e5b57c50b Poland | |
| 2cb71306-2b36-4815-b64d-03901b255be1 Finland | |
| ae16aa80-ce42-4c15-9bd5-d79399545988 Netherlands | |
| 3fbd3f6c-363d-4358-87a6-3c983eace418 Germany | |
| 23f53758-b7d2-4d5c-a1a0-a4b4706ccc60 Denmark | |
| 65e70e4f-e8f0-4264-9378-c92e31340c0e Germany | |
| 564ada3f-a3a9-4166-b1d3-77d450c62bf1 Croatia | |
| ac5b3747-0b00-4c15-83bc-288cada186a4 Czech Republic | |
| e48950c9-44ff-40a8-a0dd-f8318d1ff717 Poland | |
| a72a8f0e-8162-4eb3-8f94-416e043667d8 Netherlands | |
| 999d13f0-5465-46fd-b0d3-7707742a7f5c Netherlands | |
| cb2c0a2f-d71a-49f2-9a77-34d2772fc004 Estonia | |
| 8ea82542-dc62-4e6f-a462-4ca1940e37ed Greece | |
| 79e0ad45-3844-49d1-8ac8-0ce5f6f68588 Portugal | |
| 01b60c9c-b861-4dd6-b766-6db1a9935232 Sweden | |
| 169b85d4-88cf-4251-9810-82ceab402f13 Norway | |
| 0e6833d5-0da5-435b-9c1a-f07522283e0b Bulgaria | |
| 9908a1cc-bc79-4677-b892-d9f77cc1c5fe Sweden | |
| 0ceecb18-4f56-4959-9121-6106095a7b25 Poland | |
| 6b57a6ac-0382-461c-a5f1-9d875c535d52 France | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT5NE440AEFF000XXX |
| E-Number (Finland) | 3641320 |
| E-Number (Norway) | 4380404 |
| EAN | 8056221004732 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 186 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 6.4 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 250 mm |
| Package Level 1 Height | 245 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 6.888 kg |
| Package Level 1 EAN | 8056221004732 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1183 |
| 1SDH002065A1131 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 7000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 4P |
| Order Multiple | 1 piece |
| Power Loss | 19 W |
| Rated Current (In) | 400 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 5 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Uninterrupted Current (Iu) | 400 A |
| Release | Ekip Dip LS/I |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC60947-2 |
| Sub-type | XT5 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2824 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002011A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002011A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 400 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 160.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 400 A |
| Adjustment range undelayed short-circuit release (EF007131) | 400 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |