View larger
1SDA100362R1
100362
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2354 |
| Environmental Product Declaration - EPD | 9AKK108468A1899 |
| 9AKK108468A9748 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 59.6 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 2c09b8f4-f169-40b2-986d-2eff9ef73416 Italy |
| Simplified SCIP | 0608cc8f-5b35-4422-b599-9271aa12962d Germany |
| d753725a-4b86-4928-94a8-7a602e2af346 Belgium | |
| c9f0d2a4-bc1c-4a7b-9cd3-06888266090b Croatia | |
| a17659fa-4967-40a4-adf5-4c2e257ff4c5 Denmark | |
| d744a3e8-d936-427c-ad0e-17f4d869a695 Germany | |
| 71a6abb0-7ffd-488e-8473-61a2d9e78633 Czech Republic | |
| b2e7ae2e-71de-4a54-aa95-b3ed4566112b Poland | |
| 8ad2a394-9124-4c0f-a638-a81f21556cb5 Netherlands | |
| b6dc6949-52c7-4dbd-9b79-aecbe5b24fe7 Germany | |
| f955ac2f-c9f8-483f-8437-8c459921d4a1 Poland | |
| e457828a-35b7-4494-ac57-4484bf60debd Finland | |
| 9248b7cb-6e14-47ae-9485-c8309b4a610b Germany | |
| b6371d5f-df79-4591-9994-a678b206372d Sweden | |
| 30ed31b4-c962-4ea4-844d-51759267a8bd Poland | |
| 72ac8517-19fa-4264-9a8c-795d9dc52a22 France | |
| f141f470-37ff-444c-8596-3ed306c6a615 Sweden | |
| 4d9fd0c9-2b9a-45ad-8a37-81c6b93b55fb Estonia | |
| 67b0ccb5-5b44-417e-8c52-d60936498dcf Greece | |
| 8d72ad92-eab8-40a8-87dc-9be8cb62db7d Portugal | |
| 03120f1b-36f3-4b7e-a8b3-d42bf7439691 Bulgaria | |
| c59992bf-f3c7-4bb7-bab4-a99b0c1f4eb4 Norway | |
| 01ed5fde-73d6-4bcb-b96d-5c856a04c995 Hungary | |
| 6272729c-5212-4702-82e6-cc012e454da8 Hungary | |
| 0062885a-c91b-4258-8f8f-5d1ed48ca910 Germany | |
| b6fc972a-7472-4ae7-b991-c12f635af4af France | |
| 64c57f56-049a-4f58-9306-2f2e0e4951f8 Spain | |
| f325f0cd-e406-4dc7-87f6-63ce6775bb12 Belgium | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT5NE340AGFF000XXX |
| EAN | 8056221004398 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 140 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 4.82 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 250 mm |
| Package Level 1 Height | 245 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 5.308 kg |
| Package Level 1 EAN | 8056221004398 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1115 |
| 1SDH002065A1131 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 7000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | 19 W |
| Rated Current (In) | 400 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 5 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Uninterrupted Current (Iu) | 400 A |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC60947-2 |
| Sub-type | XT5 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2824 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002011A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002011A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 400 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 160.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 400 A |
| Adjustment range undelayed short-circuit release (EF007131) | 400 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |