View larger
1SDA100043R1 ABB XT2S 160 Ekip Dip LIG In 100A 3p F F
1SDA100043R1
100043
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Molded Case Circuit Breakers ≤ 250 A Xtmax
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This 1SDA100043R1 ABB XT2S 160 Ekip Dip LIG In 100A 3p F F functions as a molded case circuit breaker designed to automatically interrupt electrical power during overloads or short circuits. Circuit protection devices like this are widely utilized in electrical switchboards to safeguard infrastructure and maintain operational safety.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- End Of Life Disassembling Instructions: 9AKK108468A2349
- Environmental Product Declaration - EPD: 9AKK108469A1855
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 55.70 %
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK108467A6707
- Order Code US and Canada: XT2SE3100CFF000XXX
- EAN: 8056221000970
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 90 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2349 |
| Environmental Product Declaration - EPD | 9AKK108469A1855 |
| 9AKK108468A1897 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 55.70 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT2SE3100CFF000XXX |
| EAN | 8056221000970 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 90 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.12 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 130 mm |
| Package Level 1 Height | 208 mm |
| Package Level 1 Depth / Length | 145 mm |
| Package Level 1 Gross Weight | 1.22 kg |
| Package Level 1 EAN | 8056221000970 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 |
| Technical | |
| Current Type | AC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3P |
| Opening Time | CB with SOR 30 ms |
| CB with UVR 30 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 8.1 W |
| Rated Current (In) | 100 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 36 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 12 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 36 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 12 kA | |
| Rated Uninterrupted Current (Iu) | 160 A |
| Release | Ekip Dip LIG |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT2 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5901 |
| Mechanical Drawings | 1SDH000721R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000721R0001 |
| 1SDH000721R0505 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |