Safeguard secondary distribution circuits using the 1SDA068490R1 ABB XT4S250 Ekip LSIG R250 3P F F molded case circuit breaker. Compact and reliable circuit breakers are essential in industrial control panels to disconnect faulty loads and protect downstream equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 56.30 %
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- End of Life Instructions: 9AKK108468A2352
- Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Product Declaration - EPD: 9AKK108469A1858
- Environmental Information: 9AKK108467A6707
- REACH Declaration: 9AKK108466A1425
- RoHS Information: 9AKK108466A1424
- RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- SCIP: dce456b4-dbb8-4317-87d0-e5aaea033dc9 Italy (IT)
- Simplified SCIP: e4941b2a-3868-4308-b31b-6b10ce42fbde Germany (DE)
- Order Code US and Canada: XT4SE3250GFF000XXX
- EAN: 8015644023966
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 - 56.30 % |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| End of Life Instructions | 9AKK108468A2352 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 9AKK108469A1858 |
| 9AKK108468A1898 | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | dce456b4-dbb8-4317-87d0-e5aaea033dc9 Italy (IT) |
| Simplified SCIP | e4941b2a-3868-4308-b31b-6b10ce42fbde Germany (DE) |
| 0bb5fee4-b1dd-426f-8bf2-0de000c828d2 Czech Republic (CZ) | |
| e9077fca-f3ef-47f7-8bc0-40aef84671c0 Denmark (DK) | |
| 6fb7420e-1619-4719-9793-ad06e4263562 Sweden (SE) | |
| f55168de-cbd4-4322-86ed-6b20da8ac300 Portugal (PT) | |
| 7d561337-a3a8-4329-b0c9-0ccf095ec793 Germany (DE) | |
| 4a7cce56-7dcf-4bcf-b850-157c654e3c5b Croatia (HR) | |
| 2539c8f8-9de0-4d52-abd4-24322b77ac5a Germany (DE) | |
| 1b3b30d6-575f-490a-9aec-34d2aa2d73ff Belgium (BE) | |
| d7a0f5b0-4abf-4f67-ab55-61639e885f86 Spain (ES) | |
| 42f416ef-9e94-4b06-b750-e5cbd68f4bd2 Hungary (HU) | |
| 8951ced1-799e-4093-b1be-d866b84439d3 France (FR) | |
| 06cc3768-bce0-4410-88a2-77061f9dae63 Germany (DE) | |
| a61f67e6-ccfc-47c1-a689-f560143b536d Bulgaria (BG) | |
| 0b35a3cc-9e4b-451e-a80e-245adf820e07 Poland (PL) | |
| 42644fc6-24f3-4963-8aa6-d112f46a6f59 Poland (PL) | |
| 02c80d30-e763-4482-a74d-153d233f0494 Belgium (BE) | |
| 76390bd4-0d79-4170-891b-69976fa7ac49 Poland (PL) | |
| a4bc28c1-bf55-46f0-abfa-41f9d6858141 Estonia (EE) | |
| 9e8aafc5-d458-4ac4-9ea1-f59c2c0d5dcb Norway (NO) | |
| bc69d465-f9e5-4129-94d4-62a551a27291 Netherlands (NL) | |
| 4627c1c1-82c1-4c2a-b42b-2c51af72cd60 Sweden (SE) | |
| 065bd798-ed49-484a-bc98-1eb6ccb95775 Finland (FI) | |
| 1ad83167-7c6b-471f-ba5b-c7bfd2ba03ff Hungary (HU) | |
| ffead63d-0a44-4b4b-9b31-169e8d1c9c9d Greece (GR) | |
| 9fc82a30-3f13-4280-9e19-aad171eff6a5 Germany (DE) | |
| 64380c20-b271-426c-b68b-208ef3c25bb4 France (FR) | |
| Ordering | |
| Order Code US and Canada | XT4SE3250GFF000XXX |
| EAN | 8015644023966 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 105 mm |
| Product Net Height | 160 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 2.5 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 145 mm |
| Package Level 1 Height | 210 mm |
| Package Level 1 Depth / Length | 168 mm |
| Package Level 1 Gross Weight | 2.5 kg |
| Package Level 1 EAN | 8015644023966 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Connecting Capacity Main Circuit | Busbar 85..200 mm² |
| Current Type | AC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3 |
| Opening Time | CB with SOR 15 ms |
| CB with UVR 15 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 16.40 W |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Rated Current (In) | 250 A |
| Rated Frequency (f) | 50/60 Hz |
| Rated Voltage (Ur) | 690 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V AC |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 36 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 12 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 36 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 12 kA | |
| Rated Uninterrupted Current (Iu) | 250 A |
| Recommended Screw Driver | Main Circuit M8 |
| Release | Ekip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT4 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 8 N·m |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1003 |
| Technical UL/CSA | |
| Interrupting Rating acc. to UL489 | (240 V AC) 150 A |
| (480 V AC) 65 A | |
| (600 V AC) 25 A | |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5529 |
| GL Certificate | 1SDL000163R0095 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000722R0100 |
| Mechanical Drawings | 1SDH000722R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000722R0001 |
| 1SDH000721R0506 | |
| Classifications | |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |