View larger
1SDA067044R1 ABB XT2N160 MF R1 Im14 3P F F
1SDA067044R1
067044
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Molded Case Circuit Breakers ≤ 250 A Xtmax
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protecting electrical circuits against overloads and short circuits in commercial and industrial power distribution networks is the primary function of this Abb 1SDA067044R1 circuit-breaker. Such automatic switching devices safeguard wiring installations and connected machinery by rapidly interrupting dangerous fault currents.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 55.70 %
- End of Life Instructions: 9AKK108468A2348
- Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- Environmental Information: 9AKK108467A6707
- Environmental Product Declaration - EPD: 9AKK108469A1856
- REACH Declaration: 9AKK108466A1425
- RoHS Information: 9AKK108466A1424
- RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Order Code US and Canada: XT2NE3001IFF000XXX
- EAN: 8015644009502
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 - 55.70 % |
| End of Life Instructions | 9AKK108468A2348 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Environmental Information | 9AKK108467A6707 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 9AKK108469A1856 |
| 9AKK108468A1891 | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Ordering | |
| Order Code US and Canada | XT2NE3001IFF000XXX |
| EAN | 8015644009502 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 90 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.1 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 131 mm |
| Package Level 1 Height | 212 mm |
| Package Level 1 Depth / Length | 147 mm |
| Package Level 1 Gross Weight | 1.2 kg |
| Package Level 1 EAN | 8015644009502 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Motor Protection |
| Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
| Current Type | AC/DC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3 |
| Opening Time | CB with SOR 15 ms |
| CB with UVR 15 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 2 W |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Rated Current (In) | 1 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Rated Voltage (Ur) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 14 A |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| 500 V DC | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA |
| (230 V AC) 65 kA | |
| (240 V AC) 65 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 30 kA | |
| (525 V AC) 20 kA | |
| (690 V AC) 10 kA | |
| (250 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 3 Poles in Series 36 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA |
| (230 V AC) 65 kA | |
| (240 V AC) 65 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 30 kA | |
| (525 V AC) 20 kA | |
| (690 V AC) 10 kA | |
| (250 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 3 Poles in Series 36 kA | |
| Rated Uninterrupted Current (Iu) | 160 A |
| Recommended Screw Driver | Main Circuit M6 |
| Release | MF |
| Release Type | M |
| Short-Circuit Performance Level | N |
| Standards | IEC60947-2 |
| Sub-type | XT2 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 6 N·m |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5901 |
| GL Certificate | 1SDL000163R0093 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000721R0100 |
| Mechanical Drawings | 1SDH000721R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000721R0001 |
| Classifications | |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |