View larger
1SDA064692R1 ABB E3N2000 PR123/DC 3P F VR
1SDA064692R1
064692
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Service Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for specialized direct current power applications, this ABB 1SDA064692R1 air circuit breaker manages high-capacity DC electrical distribution and protects heavy-duty networks. Industrial installations utilize these specialized units to safely isolate fault currents in high-energy environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK10103A6076
- EAN: 8015644675851
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 404 mm
- Product Net Height: 418 mm
- Product Net Depth / Length: 302 mm
- Product Net Weight: 60 kg
- Package Level 1 Units: box 1 piece
- Package Level 1 Width: 515 mm
- Package Level 1 Height: 600 mm
- Package Level 1 Depth / Length: 615 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK10103A6076 |
| Ordering | |
| EAN | 8015644675851 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 404 mm |
| Product Net Height | 418 mm |
| Product Net Depth / Length | 302 mm |
| Product Net Weight | 60 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 600 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 72 kg |
| Package Level 1 EAN | 8015644609139 |
| Additional Information | |
| Product Main Type | SACE Emax |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| Technical | |
| Current Type | DC |
| Electrical Durability | Ue = 1000 V 9000 cycle |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 216 W |
| Rated Current (In) | 2000 A |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current (Ie) | 2000 A |
| Rated Operational Voltage | 750 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (500 V DC) 60 kA |
| (750 V DC) 40 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (500 V DC) 60 kA |
| (750 V DC) 40 kA | |
| Rated Uninterrupted Current (Iu) | 2000 A |
| Rated Voltage (Ur) | 750 V |
| Release | PR123/DC |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E3 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Rear flat Orientated | |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200012D0202 |
| Declaration of Conformity - CE | 1SDL000165R0015 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Instructions and Manuals | 1SDH000635R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |