View larger
1SCA022753R4440 ABB Disconnector interuptor OT630E30
1SCA022753R4440
022753
ABB
1 Pcs.
Connectors > Switch disconnector
Manual Switches
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The ABB 1SCA022753R4440 OT630E30 is a high-current disconnector interruptor engineered for demanding power distribution networks. These robust switching devices are deployed in main switchboards and industrial substations to safely break load currents and establish visible isolation points.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- End Of Life Disassembling Instructions: 1SCC301119M0201
- Environmental Information: 1SCC301232D0201
- Environmental Product Declaration - EPD: 1SCC301284D0201
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC011021D0201
- RoHS Declaration: 1SCC011020D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 1SCC011025D0201
- Data Sheet, Technical Information: 1SCC301020C0201
- Instructions and Manuals: 1SCC301042M0211
- Mechanical Drawings: 1SCC301314F0001
- Environmental Product Declaration - EPD: 1SCC301284D0201
- Degree of Protection: Front IP00
- Environmental Information: 1SCC301232D0201
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| End Of Life Disassembling Instructions | 1SCC301119M0201 |
| Environmental Information | 1SCC301232D0201 |
| Environmental Product Declaration - EPD | 1SCC301284D0201 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC301020C0201 |
| Instructions and Manuals | 1SCC301042M0211 |
| Mechanical Drawings | 1SCC301314F0001 |
| 1SCC301313F0001 | |
| OT600_800E30.igs | |
| Environmental Product Declaration - EPD | 1SCC301284D0201 |
| Environmental | |
| Degree of Protection | Front IP00 |
| Environmental Information | 1SCC301232D0201 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country or Territory of Origin | Finland |
| Dimensions | |
| Product Net Width | 266 mm |
| Product Net Height | 250 mm |
| Product Net Depth / Length | 140 mm |
| Product Net Weight | 6.1 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 260 mm |
| Package Level 1 Depth / Length | 335 mm |
| Package Level 1 Height | 152 mm |
| Package Level 1 Gross Weight | 6.5 kg |
| Package Level 1 EAN | 6417019245041 |
| Technical | |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 630 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 630 A |
| Degree of Protection | Front IP00 |
| Distance Between Phases | Standard |
| Handle Type | Handle and shaft not included |
| Mechanical Durability | 10000 |
| Mounting Type | Base mounting |
| Number of Poles | 3P |
| Operating Mode | Front |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Bottom In - Top Out | |
| Power Loss | at Rated Operating Conditions per Pole 25 W |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 630 A |
| (500 V) 630 A | |
| (690 V) 630 A | |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 630 A |
| (500 V) 630 A | |
| (690 V) 630 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 630 A |
| (500 V) 630 A | |
| (690 V) 630 A | |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 200 kW |
| (400 ... 415 V) 355 kW | |
| (500 V) 400 kW | |
| (690 V) 630 kW | |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V) 80 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 20 kA |
| Special Functions | No |
| Standards | IEC 60947-3 |
| Switches Operating Mechanism | Mechanism at the End of the Switch |
| 30 (Right Side) | |
| Terminal Type | Lug terminals |
| Tightening Torque | acc. IEC 60947-1 50 … 75 N·m |
| Technical UL/CSA | |
| Tightening Torque | acc. IEC 60947-1 50 … 75 N·m |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SCC301337D0201 |
| Declaration of Conformity - CE | 1SCC301140D2704 |
| DNV GL Certificate | 1SCC301184D0203 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
| UNSPSC | 39122233 |
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |