View larger
1SCA022613R3160 ABB Box disconnector switch OTR63A3M
1SCA022613R3160
022613
ABB
1 Pcs.
Connectors > Switch disconnector
Manual Switches
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
1SCA022613R3160 ABB Box disconnector switch OTR63A3M is an enclosed disconnector switch designed to safely interrupt electrical power supply lines near heavy industrial equipment. Enclosed load break switches are commonly deployed in harsh factory environments where physical protection against dust and moisture is required during maintenance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC340076D0201
- RoHS Declaration: 1SCC340075D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 1SCC340095D0201
- Data Sheet, Technical Information: 1SCC340015C0201
- Instructions and Manuals: 1SCC340006M0013
- Mechanical Drawings: OTLK251611P32.stp
- Degree of Protection: acc. to IEC 60529 IP65
- Pollution Degree: 3
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85363030
- Last Ordering Date: 2026-08-31 All Countries
- Replacement Product ID (NEW): OTR63GA3M
- Country or Territory of Origin: Bulgaria
- Product Net Width: 165 mm
More info
▲| Material Compliance | |
|---|---|
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC340076D0201 |
| RoHS Declaration | 1SCC340075D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC340095D0201 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC340015C0201 |
| Instructions and Manuals | 1SCC340006M0013 |
| Mechanical Drawings | OTLK251611P32.stp |
| Environmental | |
| Degree of Protection | acc. to IEC 60529 IP65 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85363030 |
| Last Ordering Date | 2026-08-31 All Countries |
| Replacement Product ID (NEW) | OTR63GA3M |
| Country or Territory of Origin | Bulgaria |
| Dimensions | |
| Product Net Width | 165 mm |
| Product Net Height | 250 mm |
| Product Net Depth / Length | 110 mm |
| Product Net Weight | 2.16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 177 mm |
| Package Level 1 Depth / Length | 263 mm |
| Package Level 1 Height | 167 mm |
| Package Level 1 Gross Weight | 2.4 kg |
| Package Level 1 EAN | 6417019199757 |
| Technical | |
| Cable Cross-Section | 10 ... 70 mm² |
| Cable Entry Position | Top and/or Bottom |
| Cable Outlets Per Side | 2xø32.5+ø16.5 / 2xø32.5+ø16.5 |
| Connecting Capacity Main Circuit | Screw Clamp 10 ... 70 mm² |
| Screw Clamp / PE Terminal 2pc,1.5 ... 25 mm² | |
| Conventional Thermal Current (Ithe) | Fully Enclosed 115 A |
| Degree of Protection | acc. to IEC 60529 IP65 |
| Enclosure Material | Stainless steel |
| Handle Color | Red / Yellow |
| Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK09 |
| Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 1 NO, 0 NC |
| Neutral Type | No Neutral Terminal |
| Number of Auxiliary Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Poles | 3P |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Position of PE Terminals | Top In - Bottom Out |
| Power Loss | at Rated Operating Conditions per Pole 4 W |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 63 A |
| (500 V) 63 A | |
| (690 V) 63 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 63 A |
| (500 V) 50 A | |
| (690 V) 35 A | |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 30 kW |
| (500 V) 30 kW | |
| (690 V) 30 kW | |
| Rated Operational Voltage | Main Circuit 750 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 3.6 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 2.5 kA |
| Recommended Screw Driver | Main Circuit Hexagon 4 |
| Special Functions | EMC |
| Standards | IEC 60947-1, -3 |
| Tightening Torque | Main Circuit 6 N·m |
| Wire Stripping Length | 20 mm |
| Technical UL/CSA | |
| Wire Stripping Length | 20 mm |
| Recommended Screw Driver | Main Circuit Hexagon 4 |
| Tightening Torque | Main Circuit 6 N·m |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 1SCC340006D2704 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
| UNSPSC | 39122205 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch |
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |