Product Overview

The 1SCA022546R1120 ABB boxed disconnector is a protective mechanical switch used to interrupt electrical current manually in harsh industrial environments. Enclosed units of this type prevent accidental electrical contact and protect internal switching contacts from dust and moisture exposure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • REACH Declaration: 1SCC340076D0201
  • RoHS Declaration: 1SCC340075D0201
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Toxic Substances Control Act - TSCA: 1SCC340095D0201
  • Data Sheet, Technical Information: 1SCC340015C0201
  • Instructions and Manuals: 1SCC340006M0013
  • Mechanical Drawings: OTLK302013PBB.stp
  • Degree of Protection: acc. to IEC 60529 IP65
  • Pollution Degree: 3
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85363030
  • Last Ordering Date: 2026-08-31 All Countries
  • Replacement Product ID (NEW): OTL80GT3M
  • Country or Territory of Origin: Bulgaria
  • Product Net Width: 200 mm

More info

▲
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC340076D0201
RoHS Declaration1SCC340075D0201
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA1SCC340095D0201
Popular Downloads
Data Sheet, Technical Information1SCC340015C0201
Instructions and Manuals1SCC340006M0013
Mechanical DrawingsOTLK302013PBB.stp
Environmental
Degree of Protectionacc. to IEC 60529 IP65
Pollution Degree3
Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85363030
Last Ordering Date2026-08-31 All Countries
Replacement Product ID (NEW)OTL80GT3M
Country or Territory of OriginBulgaria
Dimensions
Product Net Width200 mm
Product Net Height300 mm
Product Net Depth / Length135 mm
Product Net Weight3.1 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width212 mm
Package Level 1 Depth / Length313 mm
Package Level 1 Height191 mm
Package Level 1 Gross Weight3.3 kg
Package Level 1 EAN6417019174587
Technical
Cable Cross-Section10 ... 70 mm²
Cable Entry PositionTop and/or Bottom
Cable Outlets Per SideB-flange / B-flange
Connecting Capacity Main CircuitScrew Clamp 10 ... 70 mm²
Screw Clamp / PE Terminal 2pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)Fully Enclosed 125 A
Degree of Protectionacc. to IEC 60529 IP65
Enclosure MaterialSteel sheet
Handle ColorBlack
Handle TypePistol handle
Impact Resistance RatingHousing IK09
Maximum Mounted Auxiliary Contacts2 NO, 2 NC
Mounted Auxiliary Contacts1 NO, 0 NC
Neutral TypeNo Neutral Terminal
Number of Auxiliary Contacts NC0
Number of Auxiliary Contacts NO1
Number of Poles3P
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out
Position of PE TerminalsTop In - Bottom Out
Power Lossat Rated Operating Conditions per Pole 6.3 W
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 125 A
(500 V) 125 A
(690 V) 125 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 90 A
(500 V) 70 A
(690 V) 50 A
Rated Operational Power AC-23A (Pe)(380 ... 415 V) 45 kW
(500 V) 45 kW
(690 V) 45 kW
Rated Operational VoltageMain Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)(690 V AC) 3.6 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 2.5 kA
Recommended Screw DriverMain Circuit Hexagon 4
StandardsIEC 60947-1, -3
Tightening TorqueMain Circuit 6 N·m
Wire Stripping Length20 mm
Technical UL/CSA
Wire Stripping Length20 mm
Recommended Screw DriverMain Circuit Hexagon 4
Tightening TorqueMain Circuit 6 N·m
Certificates and Declarations
Declaration of Conformity - CE1SCC340005D2704
External Classifications and Standards
Object Classification CodeQ
ETIM 9EC000216 - Switch disconnector (low voltage)
ETIM 10EC000216 - Switch disconnector (AC)
UNSPSC39122205
IDEA Granular Category Code (IGCC)5166 >> Safety switch
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)3642385
E-Number (Sweden)3140555

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.