ABB OT63ML4 disconnect switch is a compact manual load break switch designed to safely isolate electrical circuits in commercial and light industrial control panels. Enclosure builders and system integrators use these versatile disconnect switches to comply with safety regulations and provide reliable local motor isolation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Environmental Information: 1SCC301263D0201
  • Environmental Product Declaration - EPD: 1SCC301279D0201
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • REACH Declaration: 1SCC011021D0201
  • RoHS Declaration: 1SCC011020D0201
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Toxic Substances Control Act - TSCA: 1SCC011025D0201
  • Data Sheet, Technical Information: 1SCC301020C0201
  • Instructions and Manuals: 1SCC301064M0212
  • Mechanical Drawings: 1SCC307719F0001
  • Environmental Product Declaration - EPD: 1SCC301279D0201
  • Degree of Protection: Front IP20
  • Environmental Information: 1SCC301263D0201
  • Pollution Degree: 3
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85365080

More info

▲
ABB EcoSolutions
Environmental Information1SCC301263D0201
Environmental Product Declaration - EPD1SCC301279D0201
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC011021D0201
RoHS Declaration1SCC011020D0201
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA1SCC011025D0201
Popular Downloads
Data Sheet, Technical Information1SCC301020C0201
Instructions and Manuals1SCC301064M0212
Mechanical Drawings1SCC307719F0001
1SCC307718F0001
OT45-80ML4.stp
OT45-80ML4.igs
Environmental Product Declaration - EPD1SCC301279D0201
Environmental
Degree of ProtectionFront IP20
Environmental Information1SCC301263D0201
Pollution Degree3
Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85365080
Country or Territory of OriginFinland
Dimensions
Product Net Width70 mm
Product Net Height91.5 mm
Product Net Depth / Length73 mm
Product Net Weight0.31 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width82 mm
Package Level 1 Depth / Length103 mm
Package Level 1 Height84 mm
Package Level 1 Gross Weight0.34 kg
Package Level 1 EAN6417019168852
Technical
Cable Cross-SectionCu 1.5 ... 35 mm²
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 80 A
Conventional Thermal Current (Ithe)Fully Enclosed 80 A
Degree of ProtectionFront IP20
Distance Between PhasesStandard
Fourth Pole PositionRight Side
Fourth Pole TypeSwitched - Simultaneous Function
Handle TypeHandle and shaft not included
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles4P
Operating ModeFront
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out
Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 2.8 W
Rated Conditional Short-Circuit Current (Inc)(100 A fuse, ≤415 V) 50 kA
(100 A fuse, 500 V) 100 kA
(80 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 80 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 80 A
(500 V) 80 A
(690 V) 80 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 75 A
(500 V) 58 A
(690 V) 20 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 11 kW
(400 ... 415 V) 22 kW
(500 V) 22 kW
(690 V) 15 kW
Rated Operational VoltageMain Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 2.1 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 1 kA
Special FunctionsNo
StandardsIEC 60947-3
Switches Operating MechanismMechanism on Top of the Switch
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 2 N·m
Technical UL/CSA
Tightening Torqueacc. IEC 60947-1 2 N·m
Certificates and Declarations
A2L Certificate – IEC1SCC301335D0201
ATEX CertificateNo certification needed
Declaration of Conformity - CE1SCC301167D2704
UL CertificateNo certification needed
VDE CertificateNo certification needed
External Classifications and Standards
Object Classification CodeQ
ETIM 9EC000216 - Switch disconnector (low voltage)
ETIM 10EC000216 - Switch disconnector (AC)
UNSPSC39122233
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Sweden)3171080

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.