ABB 1SCA022497R0650 1SCA022497R0650 ABB OT25M4 disconnect switch View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SCA022497R0650 ABB OT25M4 disconnect switch

1SCA022497R0650

022497

ABB

1 Pcs.

OT25M4 disconnect switch OT25M4 SWITCH-DISCONNECTOR

Connectors > Switch disconnector
Manual Switches

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

1SCA022497R0650 ABB OT25M4 disconnect switch is a compact modular switching component utilized for isolating low-voltage electrical circuits in control cabinets. These DIN-rail mountable disconnects ensure safe power termination for localized machine controls and instrumentation loops.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Environmental Information: 1SCC301262D0201
  • Environmental Product Declaration - EPD: 1SCC301278D0201
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • REACH Declaration: 1SCC011021D0201
  • RoHS Declaration: 1SCC011020D0201
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Toxic Substances Control Act - TSCA: 1SCC011025D0201
  • Data Sheet, Technical Information: 1SCC301020C0201
  • Instructions and Manuals: 1SCC301052M0006
  • Mechanical Drawings: OT16M4.stp
  • Environmental Product Declaration - EPD: 1SCC301278D0201
  • Degree of Protection: Front IP20
  • Environmental Information: 1SCC301262D0201
  • Pollution Degree: 3
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85365080

More info

▲
ABB EcoSolutions
Environmental Information1SCC301262D0201
Environmental Product Declaration - EPD1SCC301278D0201
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC011021D0201
RoHS Declaration1SCC011020D0201
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA1SCC011025D0201
Popular Downloads
Data Sheet, Technical Information1SCC301020C0201
Instructions and Manuals1SCC301052M0006
Mechanical DrawingsOT16M4.stp
Environmental Product Declaration - EPD1SCC301278D0201
Environmental
Degree of ProtectionFront IP20
Environmental Information1SCC301262D0201
Pollution Degree3
Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85365080
Country or Territory of OriginFinland
Dimensions
Product Net Width68 mm
Product Net Height48 mm
Product Net Depth / Length73 mm
Product Net Weight0.125 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width82 mm
Package Level 1 Depth / Length103 mm
Package Level 1 Height86 mm
Package Level 1 Gross Weight0.14 kg
Package Level 1 EAN6417019158426
Technical
Cable Cross-SectionCu 0.75 ... 10 mm²
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 32 A
Conventional Thermal Current (Ithe)Fully Enclosed 32 A
Degree of ProtectionFront IP20
Distance Between PhasesStandard
Fourth Pole PositionRight Side
Fourth Pole TypeSwitched - Simultaneous Function
Handle TypeHandle and shaft not included
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles4P
Operating ModeFront
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out
Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 0.6 W
Rated Conditional Short-Circuit Current (Inc)(40 A fuse, ≤415V) 50 kA
(25 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 25 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 25 A
(500 V) 25 A
(690 V) 25 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 20 A
(500 V) 20 A
(690 V) 11 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 4 kW
(400 ... 415 V) 9 kW
(500 V) 9 kW
(690 V) 9 kW
Rated Operational VoltageMain Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 0.5 kA
Special FunctionsNo
StandardsIEC 60947-3 / UL 508 / CSA C22.2 No. 14
Switches Operating MechanismMechanism on Top of the Switch
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 0.8 N·m
Technical UL/CSA
Horsepower Rating UL/CSA(110 ... 120 V AC) Single Phase 1.5 Hp
(240 V AC) Single Phase 3 Hp
(440 ... 480 V AC) Single Phase 7.5 Hp
(550 ... 600 V AC) Single Phase 10 Hp
(220 ... 240 V AC) Three Phase 7,5 Hp
(440 ... 480 V AC) Three Phase 15 Hp
(550 ... 600 V AC) Three Phase 20 Hp
Tightening Torqueacc. IEC 60947-1 0.8 N·m
Certificates and Declarations
A2L Certificate – IEC1SCC301335D0201
ATEX CertificateNo certification needed
Declaration of Conformity - CE1SCC301166D2703
UL CertificateNo certification needed
VDE CertificateNo certification needed
External Classifications and Standards
Object Classification CodeQ
ETIM 9EC000216 - Switch disconnector (low voltage)
ETIM 10EC000216 - Switch disconnector (AC)
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Sweden)3171078

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.