View larger
1SBL911074R8610 ABB AX12-30-10-86 400-415V50Hz 415-440V60Hz
1SBL911074R8610
911074
ABB
1 Pcs.
Automation > Power contactor, AC switching
Contactors and overload relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for industrial control applications, the ABB AX12-30-10-86 power contactor provides dependable switching for motors, lighting, and heating circuits. System designers select these devices to maintain efficient operation across automated processes.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC177925_EPLAN
- Data Sheet, Technical Information: 1SBC100187L0203
- Instructions and Manuals: 9AKK107492A7057
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 44 mm
- Product Net Depth / Length: 74 mm
- Product Net Height: 74 mm
- Product Net Weight: 0.326 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 0
- Rated Operational Voltage: Auxiliary Circuit 690 V
- Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC177925_EPLAN |
| Data Sheet, Technical Information | 1SBC100187L0203 |
| Instructions and Manuals | 9AKK107492A7057 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 44 mm |
| Product Net Depth / Length | 74 mm |
| Product Net Height | 74 mm |
| Product Net Weight | 0.326 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 26 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (220 / 240 V) 55 °C 22 A |
| (690 V) 40 °C 25 A | |
| (690 V) 70 °C 18 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 12 A |
| (440 V) 55 °C 9 A | |
| (500 V) 55 °C 9 A | |
| (690 V) 55 °C 7 A | |
| (380 / 400 V) 55 °C 12 A | |
| (220 / 230 / 240 V) 55 °C 12 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) NC 2 |
| (500 V) 2 A | |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (380 / 400 V) 3 A | |
| (400 / 440 V) 2 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (110 V) 1.1 A / 121 W | |
| (125 V) 1.1 A / 138 W | |
| (220 V) 0.55 A / 121 W | |
| (250 V) 0.55 A / 138 W | |
| (400 V) 2.8 A / 134 W | |
| (500 V) 2 A / 144 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 5.5 kW |
| (440 V) 4 kW | |
| (500 V) 5.5 kW | |
| (690 V) 5.5 kW | |
| (380 / 400 V) 5.5 kW | |
| (220 / 230 / 240 V) 3 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 120 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 55 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 280 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 70 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 400 ... 415 V |
| 60 Hz 415 ... 440 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.8 W |
| at Rated Operating Conditions AC-3 per Pole 0.1 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 16 ms |
| Between Coil De-energization and NO Contact Opening 4 ... 11 ms | |
| Between Coil Energization and NC Contact Opening 7 ... 21 ms | |
| Between Coil Energization and NO Contact Closing 10 ... 26 ms | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1 N·m |
| Control Circuit 1 N·m | |
| Main Circuit 1 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| General Use Rating UL/CSA | (600 V AC) 25 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 3/4 hp |
| (200 ... 208 V AC) Three Phase 3 hp | |
| (220 ... 240 V AC) Three Phase 3 hp | |
| (240 V AC) Single Phase 2 hp | |
| (440 ... 480 V AC) Three Phase 7.5 hp | |
| (550 ... 600 V AC) Three Phase 10 hp | |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb |
| Control Circuit 9 in·lb | |
| Main Circuit 9 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 13.8 A |
| (200 ... 208 V AC) Three Phase 11 A | |
| (220 ... 240 V AC) Three Phase 9.6 A | |
| (240 V AC) Single Phase 12 A | |
| (440 ... 480 V AC) Three Phase 11 A | |
| (550 ... 600 V AC) Three Phase 11 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| Certificates and Declarations | |
| CB Certificate | 9AKK107492A7072 |
| CCC Certificate | 9AKK107492A7089 |
| CCS Certificate | GZ23PTB00147 |
| CQC Certificate | CQC2013010304646608 |
| Declaration of Conformity - CCC | 2020980304001066 |
| Declaration of Conformity - CE | 1SBD250011U1000 |
| UL Certificate | UL_20140702-E312527-10-5 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 48 mm |
| Package Level 1 Depth / Length | 78 mm |
| Package Level 1 Height | 79 mm |
| Package Level 1 Gross Weight | 0.34 kg |
| Package Level 1 EAN | 3471522393869 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |