View larger
1SBL901074R8510 ABB AX09-30-10-85 380-400V50Hz 400-415V60Hz
1SBL901074R8510
901074
ABB
1 Pcs.
Automation > Power contactor, AC switching
Contactors and overload relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB 1SBL901074R8510 contactor serves as a core electrical switching element in automated production lines, pump systems, and commercial building management panels. Engineers use these components to establish reliable, repetitive control over electric motors and heating elements.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC177924_EPLAN
- Data Sheet, Technical Information: 1SBC100187L0203
- Instructions and Manuals: 9AKK107492A7057
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 44 mm
- Product Net Depth / Length: 74 mm
- Product Net Height: 74 mm
- Product Net Weight: 0.326 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 0
- Rated Operational Voltage: Auxiliary Circuit 690 V
- Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC177924_EPLAN |
| Data Sheet, Technical Information | 1SBC100187L0203 |
| Instructions and Manuals | 9AKK107492A7057 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 44 mm |
| Product Net Depth / Length | 74 mm |
| Product Net Height | 74 mm |
| Product Net Weight | 0.326 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 24 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (220 / 240 V) 55 °C 22 A |
| (690 V) 40 °C 22 A | |
| (690 V) 70 °C 18 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 9 A |
| (440 V) 55 °C 9 A | |
| (500 V) 55 °C 9 A | |
| (690 V) 55 °C 7 A | |
| (380 / 400 V) 55 °C 9 A | |
| (220 / 230 / 240 V) 55 °C 9 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) NC 2 |
| (500 V) 2 A | |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (380 / 400 V) 3 A | |
| (400 / 440 V) 2 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (110 V) 1.1 A / 121 W | |
| (125 V) 1.1 A / 138 W | |
| (220 V) 0.55 A / 121 W | |
| (250 V) 0.55 A / 138 W | |
| (400 V) 2.8 A / 134 W | |
| (500 V) 2 A / 144 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 4 kW |
| (440 V) 4 kW | |
| (500 V) 5.5 kW | |
| (690 V) 5.5 kW | |
| (380 / 400 V) 4 kW | |
| (220 / 230 / 240 V) 2.2 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 100 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 50 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 250 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 60 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 380 ... 400 V |
| 60 Hz 400 ... 415 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.8 W |
| at Rated Operating Conditions AC-3 per Pole 0.1 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 16 ms |
| Between Coil De-energization and NO Contact Opening 4 ... 11 ms | |
| Between Coil Energization and NC Contact Opening 7 ... 21 ms | |
| Between Coil Energization and NO Contact Closing 10 ... 26 ms | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1 N·m |
| Control Circuit 1 N·m | |
| Main Circuit 1 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| General Use Rating UL/CSA | (600 V AC) 21 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1/2 hp |
| (200 ... 208 V AC) Three Phase 2 hp | |
| (220 ... 240 V AC) Three Phase 2 hp | |
| (240 V AC) Single Phase 1.5 hp | |
| (440 ... 480 V AC) Three Phase 5 hp | |
| (550 ... 600 V AC) Three Phase 7.5 hp | |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb |
| Control Circuit 9 in·lb | |
| Main Circuit 9 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 9.8 A |
| (200 ... 208 V AC) Three Phase 7.8 A | |
| (220 ... 240 V AC) Three Phase 6.8 A | |
| (240 V AC) Single Phase 10 A | |
| (440 ... 480 V AC) Three Phase 7.6 A | |
| (550 ... 600 V AC) Three Phase 9 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 0eef99eb-512a-4268-81a9-b4f57286b68b Bulgaria |
| Simplified SCIP | 051ffbb7-269c-4866-9671-c2b169f0498f Italy |
| 12aa04ba-2e93-4603-befe-ab1d381e82a5 Germany | |
| 234ad64a-ee54-45b5-ab96-c201a94c06b5 Denmark | |
| 2aedcd5f-d39f-4fbc-b679-f756a6c0bf2f Netherlands | |
| 35e8cb82-6ec5-41e9-a918-6ba79788a7a9 Spain | |
| 39227b12-2f2a-4556-a2fd-297687a026a9 Portugal | |
| 4729e7f7-c43f-4dff-ba1b-4cec6d44bf94 Hungary | |
| 58a43693-f871-4420-b137-99ca69d86538 Finland | |
| 5f367979-b9b3-4bb9-97e0-5fd32fdf8f89 Estonia | |
| 7f721881-3e2d-49e6-9b19-e0ab2431eb80 Czech Republic | |
| 92799bfc-ce29-446d-bf09-5e30ae744df7 Sweden | |
| 9e813846-051e-4f2e-a44b-20ce09d19146 France | |
| b44be7d0-4b69-4ea2-9b07-6713e54938a0 Belgium | |
| b6f8b154-d3f9-4fe5-a26b-57e1fe91e705 Croatia | |
| e2dc2aeb-7bfa-442c-a88e-be03833afc7d Norway | |
| ed9b9470-0ddb-44a3-bbec-92fd58e10907 Greece | |
| fed833f0-9cf0-4ac4-9e09-18e985e1a2df Poland | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| Certificates and Declarations | |
| CB Certificate | 9AKK107492A7072 |
| CCC Certificate | 9AKK107492A7089 |
| CCS Certificate | GZ23PTB00147 |
| CQC Certificate | CQC2013010304646608 |
| Declaration of Conformity - CCC | 2020980304001066 |
| Declaration of Conformity - CE | 1SBD250011U1000 |
| UL Certificate | UL_20140702-E312527-10-5 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 48 mm |
| Package Level 1 Depth / Length | 78 mm |
| Package Level 1 Height | 79 mm |
| Package Level 1 Gross Weight | 0.34 kg |
| Package Level 1 EAN | 3471522391858 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |