View larger
1SBL401001R8011 ABB AFC96-30-11-80 220-230V50Hz 230-240V60Hz
1SBL401001R8011
1SBL401001R8011
ABB
1 Pcs.
Automation > Power contactor, AC switching
Contactors and overload relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A contactor functions as a heavy-duty electrical relay designed for frequent switching of high-power electrical loads such as industrial machinery, large heating systems, and multi-phase motors. Technicians integrate parts like the ABB 1SBL401001R8011 into automated control architectures to safely manage power distribution across complex installations.
Exact pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Data Sheet, Technical Information: 1SBC100219C0201
- Instructions and Manuals: 1SBC101036M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- Product Net Width: 87 mm
- Product Net Depth / Length: 119.5 mm
- Product Net Height: 116 mm
- Product Net Weight: 1.25 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 1
- Number of Poles: 3P
- Rated Operational Voltage: Main Circuit 1000 V
- Conventional Free-air Thermal Current (I th ): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100219C0201 |
| Instructions and Manuals | 1SBC101036M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| Dimensions | |
| Product Net Width | 87 mm |
| Product Net Depth / Length | 119.5 mm |
| Product Net Height | 116 mm |
| Product Net Weight | 1.25 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, UL 60335-2-40 LZGH2 A2L |
| Rated Operational Voltage | Main Circuit 1000 V |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 130 A |
| (690 V) 60 °C 105 A | |
| (690 V) 70 °C 90 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 96 A |
| (440 V) 60 °C 96 A | |
| (500 V) 60 °C 80 A | |
| (690 V) 60 °C 57 A | |
| (1000 V) 60 °C 30 A | |
| (380 / 400 V) 60 °C 96 A | |
| (220 / 230 / 240 V) 60 °C 96 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 96 A |
| (440 V) 60 °C 96 A | |
| (500 V) 60 °C 80 A | |
| (690 V) 60 °C 57 A | |
| (380 / 400 V) 60 °C 96 A | |
| (220 / 230 / 240 V) 60 °C 96 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) NC 2 |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 55 kW |
| (440 V) 55 kW | |
| (500 V) 55 kW | |
| (690 V) 55 kW | |
| (1000 V) 40 kW | |
| (380 / 400 V) 45 kW | |
| (220 / 230 / 240 V) 25 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 55 kW |
| (440 V) 55 kW | |
| (500 V) 55 kW | |
| (690 V) 55 kW | |
| (380 / 400 V) 45 kW | |
| (220 / 230 / 240 V) 25 kW | |
| Rated Operational Power AC-6b (Pe) | (400 / 415 V) 40 °C, 50 / 60 Hz 60 kvar |
| (400 / 415 V) 70 °C, 50 / 60 Hz 53 kvar | |
| (400 / 415 V) 55 °C, 50 / 60 Hz 60 kvar | |
| (440 V) 40 °C, 50 / 60 Hz 65 kvar | |
| (440 V) 55 °C, 50 / 60 Hz 65 kvar | |
| (440 V) 70 °C, 50 / 60 Hz 58 kvar | |
| (500 / 550 V), 40 °C, 50 / 60 Hz 75 kvar | |
| (500 / 550 V) 55 °C, 50 / 60 Hz 75 kvar | |
| (500 / 550 V) 70 °C, 50 / 60 Hz 70 kvar | |
| (690 V) 40 °C, 50 / 60 Hz 82 kvar | |
| (690 V) 55 °C, 50 / 60 Hz 82 kvar | |
| (690 V) 70 °C, 50 / 60 Hz 75 kvar | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 150 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 220 ... 230 V |
| 60 Hz 230 ... 240 V | |
| Coil Consumption | Average Holding Value 50 / 60 Hz 20 V·A |
| Average Pull-in Value 50 Hz 236 V·A | |
| Average Pull-in Value 60 Hz 260 V·A | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 8.2 W |
| at Rated Operating Conditions AC-3 per Pole 4.5 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 21 ms |
| Between Coil De-energization and NO Contact Opening 5 ... 16 ms | |
| Between Coil Energization and NC Contact Opening 3 ... 17 ms | |
| Between Coil Energization and NO Contact Closing 7 ... 22 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 6 ... 50 mm² |
| Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | |
| Rigid 1x 6 ... 70 mm² | |
| Rigid 2x 6 ... 50 mm² | |
| Rigid 1x 6 ... 70 mm² | |
| Rigid 2x 6 ... 50 mm² | |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 17 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Recommended Screw Driver | Pozidriv PZ |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 6 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 115 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 7-1/2 hp |
| (200 ... 208 V AC) Three Phase 30 hp | |
| (220 ... 240 V AC) Three Phase 40 hp | |
| (240 V AC) Single Phase 20 hp | |
| (440 ... 480 V AC) Three Phase 75 hp | |
| (550 ... 600 V AC) Three Phase 75 hp | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 53 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 80 A |
| (200 ... 208 V AC) Three Phase 92 A | |
| (220 ... 240 V AC) Three Phase 80 A | |
| (240 V AC) Single Phase 88 A | |
| (440 ... 480 V AC) Three Phase 77 A | |
| (550 ... 600 V AC) Three Phase 77 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor without Thermal O/L Relay -40 ... 70 °C |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 25 g |
| Closed, Shock Direction: B1 25 g | |
| Closed, Shock Direction: B2 15 g | |
| Closed, Shock Direction: C1 25 g | |
| Closed, Shock Direction: C2 25 g | |
| Open, Shock Direction: B1 5 g | |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4888 |
| 9AKK108469A4889 | |
| BV Certificate | BV_2634H36994B2 |
| CB Certificate | CB_SE-113159 |
| CCS Certificate | GZ23PTB00147 |
| Declaration of Conformity - CE | 1SBD250024U1000 |
| Declaration of Conformity - UKCA | 1SBD250045U1000 |
| DNV Certificate | 9AKK108470A6934 |
| KC Certificate | 9AKK108471A9559 |
| RINA Certificate | 9AKK108470A5006 |
| UL Certificate | UL-US-2206508-0 |
| UL-CA-2206439-0 | |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 146.5 mm |
| Package Level 1 Depth / Length | 96.5 mm |
| Package Level 1 Height | 146.5 mm |
| Package Level 1 Gross Weight | 1.37 kg |
| Package Level 1 EAN | 3471523019553 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |