1SBL136005R2110 ABB AF09Z-30-10K-21 24-60V50/60HZ 20-60VDC
1SBL136005R2110
136005
ABB
1 Pcs.
AF09Z-30-10K-21 24-60V50/60HZ 20-60VDC
AF09Z-30-10K-21 24-60V50/60HZ 20-60VDC Contactor
Automation > Power contactor, AC switching
Contactors and overload relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
ABB AF09Z-30-10K-21 is a compact three-pole contactor used in electrical engineering to manage motor drives and automation control circuits safely. It accommodates wide control voltage ranges to suit diverse operational requirements.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 20 V
- Voltage type for actuating (EF008242): AC/DC
- Rated operation current Ie at AC-1, 400 V (EF001393): 25 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 9 A
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Rated operation power NEMA (EF011960): 1.4914 kW
- Modular version (EF001126): No
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Number of normally open contacts as main contact (EF001374): 3
More info
▲- Extended Product Type:
- AF09Z-30-10K-21
- Product ID:
- 1SBL136005R2110
- EAN:
- 3471523155510
- Catalog Description:
- AF09Z-30-10K-21 24-60V50/60HZ 20-60VDC Contactor
- Long Description:
- AF09Z..K 3-pole contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF..Z contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...250 V 50/60 Hz or 12...250 V DC. AF..Z contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF..Z contactors allow direct control by PLC-output ≥ 24 V DC 500 mA and obtain a reduced holding coil consumption. AF..Z contactors withstand short voltage dips and voltage sags (SEMI F47-0706 compliance) between 24...250 V 50/60 Hz. AF..Z contactors have built-in surge protection and do not require additional surge suppressors. AF09Z..K include Push-in Spring terminals. Only one push is all you need for extremely fast wiring: faster than ever installation, easier than ever wiring, reliable as ever connections. The AF... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks. (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Accessories: a wide range of accessories is available.
Classifications
- Object Classification Code:
- Q
- ETIM 4:
- EC000066 - Magnet contactor, AC-switching
- ETIM 5:
- EC000066 - Magnet contactor, AC-switching
- ETIM 6:
- EC000066 - Power contactor, AC switching
- ETIM 7:
- EC000066 - Power contactor, AC switching
- UNSPSC:
- 39121529
- E-Number (Sweden):
- 3210587
Container Information
- Package Level 1 Units:
- box 1 piece
- Package Level 1 Width:
- 93 mm
- Package Level 1 Depth / Length:
- 86 mm
- Package Level 1 Height:
- 45 mm
- Package Level 1 Gross Weight:
- 0.33 kg
- Package Level 1 EAN:
- 3471523155510
- Package Level 2 Units:
- box 21 piece
- Package Level 2 Width:
- 250 mm
- Package Level 2 Depth / Length:
- 300 mm
- Package Level 2 Height:
- 315 mm
- Package Level 2 Gross Weight:
- 14.85 kg
- Package Level 3 Units:
- 1080 piece
Certificates and Declarations (Document Number)
- CB Certificate:
- CB_SE-96551
- CCC Certificate:
- CCC_2010010304445624
- cUL Certificate:
- UL_20180227_E312527_7_1
- Declaration of Conformity - CE:
- 1SBD250000U1000
- DNV Certificate:
- DNV-GL_TAE00001AF-3
- DNV GL Certificate:
- DNV-GL_TAE00001AF-3
- GL Certificate:
- DNV-GL_TAE00001AF-3
- Instructions and Manuals:
- 1SBC101054M6801
- RINA Certificate:
- RINA_ELE240318XG
- RMRS Certificate:
- RMRS_1802705280
- RoHS Information:
- 1SBD250000U1000
Technical UL/CSA
- General Use Rating UL/CSA:
- (600 V AC) 25 A
- Horsepower Rating UL/CSA:
- (220 ... 240 V AC) Three Phase 2 hp
(440 ... 480 V AC) Three Phase 5 hp
(550 ... 600 V AC) Three Phase 7-1/2 hp
(120 V AC) Single Phase 3/4 hp
(200 ... 208 V AC) Three Phase 2 hp
(240 V AC) Single Phase 1-1/2 hp
Environmental
- Ambient Air Temperature:
- Close to Contactor for Storage -60 ... +80 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
- Climatic Withstand:
- Category B according to IEC 60947-1 Annex Q
- Maximum Operating Altitude Permissible:
- 3000 m
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 5 ... 300 Hz 4 g closed position / 2 g open position
- RoHS Status:
- Following EU Directive 2011/65/EU
Technical
- Number of Main Contacts NO:
- 3
- Number of Main Contacts NC:
- 0
- Number of Auxiliary Contacts NO:
- 1
- Number of Auxiliary Contacts NC:
- 0
- Rated Operational Voltage:
- Main Circuit 690 V
Auxiliary Circuit 690 V
- Rated Frequency (f):
- Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-5-1, q = 40 °C 16 A
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
- Rated Operational Current AC-1 (Ie):
- (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
- Rated Operational Current AC-3 (Ie):
- (220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
- Rated Operational Power AC-3 (Pe):
- (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
- Rated Operational Current AC-15 (Ie):
- (220 / 240 V) 4 A
(24 / 127 V) 6 A
(500 V) 2 A
(690 V) 2 A
(400 / 440 V) 3 A
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
- Maximum Electrical Switching Frequency:
- AC-1 600 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
AC-15 1200 cycles per hour
DC-13 900 cycles per hour
- Rated Operational Current DC-13 (Ie):
- (125 V) 0.55 A / 69 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(220 V) 0.27 A / 60 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
- Rated Insulation Voltage (Ui):
- acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
- Rated Impulse Withstand Voltage (Uimp):
- 6 kV
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
- Rated Control Circuit Voltage (Uc):
- 50 Hz 24 ... 60 V
50 Hz / 60 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
- Operate Time:
- Between Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
- Connecting Capacity Main Circuit:
- Flexible 1/2x 0.5 ... 4 m²
Rigid 1/2x 1 ... 6 m²
Flexible with Ferrule 1/2x 0.5 ... 4 m²
Flexible with Insulated Ferrule 1x 0.5 ... 4 m²
Flexible with Insulated Ferrule 2x 0.5 ... 2.5 m²
- Connecting Capacity Auxiliary Circuit:
- Flexible with Ferrule 1/2x 0.5 ... 2.5
Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5
Flexible 1/2x 0.5 ... 2.5 m²
Rigid 1/2x 1 ... 2.5 m²
- Connecting Capacity Control Circuit:
- Flexible with Ferrule 1/2x 0.5 ... 2.5 m²
Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 m²
Flexible 1/2x 0.5 ... 2.5 m²
Rigid 1/2x 1 ... 2.5 m²
- Wire Stripping Length:
- Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 12 mm
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
- Terminal Type:
- Push-in Spring Terminals
Dimensions
- Product Net Width:
- 45mm
- Product Net Depth / Length:
- 77mm
- Product Net Height:
- 92.3mm
- Product Net Weight:
- 0.315kg
Popular Downloads
- Instructions and Manuals:
- 1SBC101054M6801
Ordering
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85364900