ABB 1SAM350010R1008 1SAM350010R1008 ABB MS132-4.0K Push-In Motor Guard View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SAM350010R1008 ABB MS132-4.0K Push-In Motor Guard

1SAM350010R1008

350010

ABB

1 Pcs.

MS132-4.0K Push-In Motor Guard MS132-4.0 K motor protection circuit breaker Push-In MS132-4.0K Manual Motor Starter 2.5 ... 4.0 A

Automation > Motor protection circuit-breaker
Electronic motor protection relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The ABB MS132-4.0K (1SAM350010R1008) Push-In Motor Guard serves as a compact motor protection circuit breaker that combines manual control with robust thermal-magnetic trip characteristics.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362010
  • Data Sheet, Technical Information: 1SBC100212C0203
  • Instructions and Manuals: 2CDC131120M6801
  • Instructions and Manuals (Part 2): 2CDC131060M0202
  • Ex Operating Instructions: 2CDC131063M6801
  • Time-Current Characteristic Curve: 1SAM300505F0108
  • I²t Characteristic: 1SAM300507F0001
  • Cut-off Current Characteristic: 1SAM300508F0001
  • CAD Dimensional Drawing: 2CDC001079B0201
  • Installation Video: 9AKK108466A6074
  • Marketing Video: 9AKK107991A4712
  • Product Net Width: 45 mm
  • Product Net Height: 112 mm
  • Product Net Depth / Length: 87 mm
  • Product Net Weight: 0.286 kg

More info

▲
Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85362010
Popular Downloads
Data Sheet, Technical Information1SBC100212C0203
Instructions and Manuals2CDC131120M6801
Instructions and Manuals (Part 2)2CDC131060M0202
Ex Operating Instructions2CDC131063M6801
Time-Current Characteristic Curve1SAM300505F0108
I²t Characteristic1SAM300507F0001
1SAM300507F0003
Cut-off Current Characteristic1SAM300508F0001
1SAM300508F0003
CAD Dimensional Drawing2CDC001079B0201
Installation Video9AKK108466A6074
9AKK108466A6068
Marketing Video9AKK107991A4712
2CDC131153V0201
Dimensions
Product Net Width45 mm
Product Net Height112 mm
Product Net Depth / Length87 mm
Product Net Weight0.286 kg
Technical
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 100 kA
(250 V DC) 3 Poles in Series 10 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)50 A
Setting Range2.5 ... 4.0 A
Rated Operational Power AC-3 (Pe)(400 V) Three Phase 1.5 kW
Rated Operational Power AC-3e (Pe)(400 V) Three Phase 1.5 kW
Rated Operational VoltageMain Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie)4 A
Rated Operational Current AC-3 (Ie)4 A
Rated Operational Current AC-3e (Ie)4 A
Rated Operational Current DC-5 (Ie)4 A
Rated Frequency (f)Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw)0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles3P
Conventional Free-air Thermal Current (Ith)Main Circuit 4 A
Degree of ProtectionHousing IP20
Main Circuit Terminals IP20
Pollution Degree3
Electrical Durability50000 cycle
Mechanical DurabilityNr. Operations 100000 cycle
Terminal TypePush-in Spring Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.5 ... 4 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 4 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm²
Flexible 1/2x 0.75 ... 4 mm²
Solid 1/2x 1 ... 2.5 mm²
Stranded 1/2x 1 ... 6 mm²
Wire Stripping LengthMain Circuit 12 mm
Recommended Screw DriverPozidriv 2
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator TypeRotary Handle
Contact Position IndicationON / OFF / TRIP
StandardsIEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
RemarksUL508 Self-Protected Combination Motor Controller (Type E) in combination with terminal spacer TS1-M3-K
Technical UL/CSA
Short-Circuit Current Rating (SCCR)Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kA
Manual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Horsepower Rating UL/CSA(200 V AC) Three Phase 0.75 Hp
(208 V AC) Three Phase 0.75 Hp
(220 ... 240 V AC) Three Phase 1 Hp
(440 ... 480 V AC) Three Phase 2 Hp
(550 ... 600 V AC) Three Phase 3 Hp
Full Load Amps Motor Use(200 V AC) Three Phase 4 A
(208 V AC) Three Phase 4 A
(220 ... 240 V AC) Three Phase 4 A
(440 ... 480 V AC) Three Phase 4 A
(550 ... 600 V AC) Three Phase 3.9 A
Locked Rotor Amps(200 V AC) Three Phase 24 A
(208 V AC) Three Phase 24 A
(220 ... 240 V AC) Three Phase 24 A
(440 ... 480 V AC) Three Phase 24 A
(550 ... 600 V AC) Three Phase 25.6 A
General Use Rating UL/CSA(600 V AC) 4 A
Connecting Capacity Main Circuit UL/CSAStranded 1/2x 18-10 AWG
Stranded 1x 8 AWG
Environmental
Ambient Air TemperatureAround the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SAA963005-4502
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006539
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
End Of Life Disassembling Instructions1SAC200333H0001
Environmental Product Declaration - EPD1SAC200360H0001
1SAC200385H0001
Certificates and Declarations
A2L Certificate – IEC1SAA963000-4601
ABS Certificate1SAA963001-0101
ATEX Certificate1SAA963000-3902
CB Certificate1SAA963002-2002
CCC Certificate2024010307658958
CQC CertificateCQC2017010307034621
Cut-off Current Characteristic1SAM300508F0001
1SAM300508F0003
Declaration of Conformity - CCC2020980307004600
Declaration of Conformity - CE1SAD101100-3402
Declaration of Conformity - UKCA1SAD201100-3402
DNV GL Certificate1SAA963001-0304
EAC Certificate1SAA963004-2701
IECEx Certificate1SAA963000-4001
KC Certificate1SAA963002-1502
RINA Certificate1SAA963002-0802
UL CertificateE137861-20090225
E345003-20090225
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width50 mm
Package Level 1 Depth / Length117 mm
Package Level 1 Height82 mm
Package Level 1 Gross Weight0.312 kg
Package Level 1 EAN4013614400384
Package Level 2 Unitscarton 28 piece
Package Level 2 Width280 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Height210 mm
Package Level 2 Gross Weight14.026 kg
Package Level 2 EAN4013614522703
External Classifications and Standards
Object Classification CodeF
ETIM 9EC000074 - Motor protection circuit-breaker
ETIM 10EC000074 - Motor protection circuit-breaker
eClassV11.0 : 27370401
UNSPSC39121521
IDEA Granular Category Code (IGCC)4731 >> Manual Starters
E-Number (Finland)3707838
E-Number (Sweden)3110457

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.