View larger
PSR-SCF-24UC/URM/4X1/2X2
2981444
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2981444 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 279 (C-6-2017) |
| GTIN | 4017918987787 |
| Weight per Piece (excluding packing) | 127.000 g |
| Custom tariff number | 85364900 |
| Country of origin | DE (Germany) |
| Ambient temperature (operation) | -20 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Rated control circuit supply voltage US | 24 V AC/DC -20 % / +10 % |
|---|---|
| Rated control supply current IS | typ. 52 mA |
| Power consumption at US | typ. 1.25 W |
| Typ. starting time with Us | typ. 10 ms (when controlled via A1) |
| Typical release time | typ. 10 ms (when controlled via A1) |
| Recovery time | < 500 ms |
| Operating voltage display | 1 x green LED |
| Maximum switching frequency | 0.5 Hz |
| Contact type | 4 enabling current paths |
|---|---|
| 2 confirmation current paths | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2 |
| Interrupting rating (ohmic load) max. | For additional values, see load curve |
| Maximum interrupting rating (inductive load) | 48 W (N/O contact, 24 V DC, τ = 40 ms) |
| 40 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 36 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 35 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 33 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Mechanical service life | 10x 106cycles |
| Switching capacity according to IEC 60947-5-1 | 5 A (24 V (DC13)) |
| 5 A (250 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) |
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 127 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | green |
| Connection method | Screw connection |
|---|---|
| pluggable | no |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 1 |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 1 |
| Designation | EN ISO 13849 |
| Performance level (PL) | c |
| Category | 1 |
| Safety Integrity Level Claim Limit (SIL CL) | 1 |
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 250 V |
| 250 V | |
| Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit (A1/A2) and all output current paths |
| Basic insulation 4 kV between all output current paths | |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 2 ms.) |
| Conformance | CE-compliant |
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Screw connection |
| Complete with socket (EF003359) | Yes |
| With detachable clamps (EF003340) | No |
| With LED indication (EF005950) | Yes |
| Voltage type for actuating (EF008242) | AC/DC |
| Number of contacts as normally closed contact (EF008255) | 2 |
| Number of contacts as normally open contact (EF008256) | 4 |
| Number of contacts as change-over contact (EF008257) | 0 |
| With forced-guided contacts (EF003357) | No |
| Nominal current (EF000001) | 0.052 A |
| Degree of protection (IP) (EF005474) | IP20 |
| Width (EF000008) | 40 mm |
| Height (EF000040) | 111 mm |
| Depth (EF000049) | 55 mm |