1 Pcs.

Surge protection device Surge protection device, consisting of connector and base element, to protect a two-wire circuit of analogue and digital telecommunication interfaces (VDSL up to 50 MBit/s, in short sections (<300 m) up to 100 MBit/s). Surge protection device consisting of connector and base element for the protection of dual wires of analogue and digital telecommunications interfaces (VDSL up to 50 Mbit/s, on short lines (<300 m) up to 100 Mbit/s).

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2882828
Packing unit10 pc
Catalog pagePage 164 (C-4-2017)
GTIN4046356115148
Weight per Piece (excluding packing)60.040 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth65.5 mm
Horizontal pitch1 Div.
Complete module height90 mm
Complete module width17.7 mm
Complete module depth65.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Number of positions2
Direction of actionLine-Line & Line-Earth Ground

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
VDE requirement classB2
C1
C2
C3
D1
Nominal voltage UN185 V DC
130 V AC
Maximum continuous voltage UC185 V DC
130 V AC
Rated current450 mA AC (45°C)
130 mA DC (45°C)
Operating effective current ICat UC≤ 10 µA
Residual current IPE≤ 10 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-line)1 kA
Pulse discharge current Iimp(10/350) µs (line-earth)1 kA
Total discharge current Itotal(8/20) µs18 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)18 kA
Nominal pulse current Ian (10/700) µs (line-line)100 A
Nominal pulse current Ian (10/700) µs (line-earth)100 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 300 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 300 V
Output voltage limitation at 1 kV/µs (line-line) static≤ 300 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 300 V
Residual voltage at In(line-line)≤ 160 V (C2 - 10 kV / 5 kA)
Residual voltage at In(line-earth)≤ 200 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-line)≤ 250 V (B2 - 1 kV / 25 A)
≤ 300 V (B2 - 4 kV / 100 A)
≤ 270 V (C1 - 1 kV/500 A)
≤ 300 V (C2 - 2 kV/1 kA)
≤ 320 V (C2 - 4 kV / 2 kA)
≤ 330 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth)≤ 250 V (B2 - 1 kV / 25 A)
≤ 300 V (B2 - 4 kV / 100 A)
≤ 270 V (C1 - 1 kV/500 A)
≤ 300 V (C2 - 2 kV/1 kA)
≤ 320 V (C2 - 4 kV / 2 kA)
≤ 330 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 500 ns
Response time tA(line-earth)≤ 500 ns
Input attenuation aE, sym.typ. 0.4 dB (≤ 5 MHz / 100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 20 MHz
Capacity (line-line)typ. 30 pF (f=1 MHz / VR= 0 V)
Capacity (line-earth)typ. 30 pF (f=1 MHz / VR= 0 V)
Resistance in series2.2 Ω ±10 %
Surge protection fault messagenone
Impulse durability (line-line)B2 - 4 kV/100 A
C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 25 A
D1 - 1 kA
Impulse durability (line-earth)B2 - 4 kV/100 A
C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 25 A
D1 - 1 kA

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 61643-21 2000
EN 61643-21 2002

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2882828 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 185 V

Product Datasheet