View larger
VAL-CP-MOSO 60-3C-FM
2804416
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2804416 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 68 (C-4-2017) |
| GTIN | 4046356317832 |
| Weight per Piece (excluding packing) | 1,200.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 75 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-C |
| TT | |
| Mode of protection | L-PEN |
| Mounting type | 60 mm system technology (power rail) |
| Color | blue-gray |
| jet black RAL 9005 | |
| Housing material | PBT |
| PA 6 | |
| PA 6.6 | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Module for 60 mm system technology |
| Number of positions | 3 |
| Surge protection fault message | Optical, remote indicator contact |
| Nominal voltage UN | 240/415 V AC (TN-C) |
|---|---|
| 240/415 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 350 V AC |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 25 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 2.5 kV |
| Residual voltage Ures | ≤ 2.1 kV (at In) |
| ≤ 1.9 kV (at 10 kA) | |
| ≤ 1.8 kV (at 5 kA) | |
| ≤ 1.7 kV (at 3 kA) | |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) |
| 440 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | not required |
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC |
| 125 V DC (200 mA DC) | |
| Operating current | 5 mA AC ... 1 A AC |
| 1 A DC (30 V DC) | |
| Connection method | Pluggable screw connection |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Connection name | PEN conductor connection |
|---|---|
| Connection method | Screw connection |
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section solid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Connection name | Phase conductor connection |
| Connection method | 60 mm power rail system |
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| System configuration DC (EF009926) | No |
| System configuration IT (EF009927) | No |
| System configuration TN (EF009928) | No |
| System configuration TN-C (EF009929) | Yes |
| System configuration TN-C-S (EF009933) | No |
| System configuration TN-S (EF009930) | No |
| System configuration TT (EF009931) | No |
| System configuration other (EF009932) | No |
| Nominal discharge surge current (8/20) (EF004214) | 20 kA |
| Max. discharge surge current (8/20) (EF012274) | 25 kA |
| Max. continuous voltage AC (EF004198) | 350 V |
| Voltage protection level L-N (EF004236) | 2.5 kV |
| Short-circuit breaking capacity (Isccr) (EF012627) | 25 kA |
| Integrated backup fuse (EF008797) | Yes |
| Leakage-current free (EF016002) | No |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 2.5 mm² |
| Max. conductor cross section flexible (fine-strand) (EF008828) | 16 mm² |
| With remote signalling contact (EF000422) | Yes |
| Signalling at the device (EF004241) | Optic |
| Category type 2 (EF004230) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |