PHOENIX CONTACT PT-IQ-4X1+F-24DC-UT PT-IQ-4X1+F-24DC-UT 2800983 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT-IQ-4X1+F-24DC-UT 2800983 PHOENIX CONTACT Surge protection device

PT-IQ-4X1+F-24DC-UT

2800983

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection, consisting of plug-in protection and base element, with indica. Multi-level diagnostics and status integrated in module for four signal conductors with joint reference potential. Indir grounding. with gas discharger. Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for four signal wires with common reference potential. Indirect grounding via gas discharge tube. Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
General
NoteRemote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Product properties
Product typeSurge protection for MCR technology
Product familyPLUGTRAB IQ
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, multi-stage
Data management status
Article revision08
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawingdjskbjiuwq.jpg
Width17.7 mm
Height91.1 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Material specifications
Colorblack (RAL 9005)
black (RAL 9005)
Flammability rating according to UL 94V-0
Housing materialPA 6.6

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC30 V DC
21 V AC
Rated current700 mA (50 °C)
Operating effective current ICat UC≤ 1 mA (per path)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-ground)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-earth)≤ 800 V (C1 - 1 kV / 500 A)
≤ 950 V (C2 - 10 kV / 5 kA)
≤ 650 V (C2 - 10 kA)
≤ 780 V (C3 - 25 A)
Voltage protection level Up(line-signalground)≤ 75 V (C1 - 1 kV / 500 A)
≤ 135 V (C2 - 10 kV / 5 kA)
≤ 180 V (C2 - 10 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 50 A)
Voltage protection level Upstatic (line-earth)≤ 80 V (C2 - 10 kV / 5 kA)
≤ 230 V (C2 - 10 kA)
Response time tA(line-earth)≤ 100 ns
Response time tA(line-signalground)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω systemtyp. 1.1 MHz
Capacity (Core-Earth)typ. 2 nF
Resistance per path1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse800 mA (FF)
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 50 A
D1 - 2.5 kA
Impulse durability (line-signalground)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 50 A
D1 - 2,5 kA
Pulse reset time (line-earth)≤ 30 ms
Pulse reset time (line-signalground)≤ 350 ms

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + A1:2008, modified
Standards/specificationsEN 61643-21
Note2001 + A1:2009
Standards/specificationsEN 61000-6-3
Note2007 + A1:2011
Standards/specificationsEN 61000-6-2
Note2005

Mounting
Mounting typeDIN rail: 35 mm

ETIM for 2800983 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 24 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.