PHOENIX CONTACT PT-IQ-4X1-24DC-UT PT-IQ-4X1-24DC-UT 2800982 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT-IQ-4X1-24DC-UT 2800982 PHOENIX CONTACT Surge protection device

PT-IQ-4X1-24DC-UT

2800982

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection, consisting of plug-in protection and base element, with indica. Multi-level diagnostics and status integrated in module for four signal conductors with joint reference potential.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2800982
Packing unit1 pc
Catalog pagePage 111 (C-4-2017)
GTIN4046356665773
Weight per Piece (excluding packing)120.300 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height91.1 mm
Width17.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground

Additional descriptions

NoteRemote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V AC
Rated current700 mA (50 °C)
Operating effective current ICat UC≤ 1 mA (per path)
Residual current IPE≤ 1 mA (per path)
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-line)
Voltage protection level Up(line-earth)≤ 75 V (C1 - 1 kV/500 A)
≤ 135 V (C2 - 10 kV / 5 kA)
≤ 180 V (C2 - 10 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 50 A)
Voltage protection level Upstatic (line-earth)≤ 85 V (C2 - 10 kA)
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 1.1 MHz
Capacity (line-earth)typ. 2 nF
Resistance in series1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse800 mA (FF)
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C2 - 10 kA
C3 - 50 A
D1 - 2.5 kA
Pulse reset time (line-earth)≤ 350 ms

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Connection, equipotential bonding

Connection methodDIN rail NS35

Remote indication contact

Switching functionvia DIN rail connector

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008, modified
EN 61643-21 2001 + A1:2009
EN 61000-6-3 2007 + A1:2011
EN 61000-6-2 2005

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2800982 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 24 V

Product Datasheet