PHOENIX CONTACT CT 10-18FSR+F/PE-24 CT 10-18FSR+F/PE-24 2807939 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CT 10-18FSR+F/PE-24 2807939 PHOENIX CONTACT Surge protection plug

CT 10-18FSR+F/PE-24

2807939

PHOENIX CONTACT

1 Pcs.

Surge protection plug LSA-PLUS (COMTRAB CT 10) connector with coarse/fine surge protection and decoupling resistance for 18 signal lines - GND and coarse GND protection - PE. Nominal voltage: 24 V DC. Version: 10 two-wire circuits

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2807939
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 107 (C-6-2013)
GTIN4017918075415
Weight per Piece (excluding packing)1.330 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height22 mm
Width111 mm
Depth68.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 75 °C
Degree of protectionIP20

General

Housing materialPBT
Flammability rating according to UL 94V0
Colorblack
Standards for cearances and creepage distancesVDE 0110-1
Mounting typeOn CT-TERMIBLOCK and LSA-PLUS disconnect strip
TypeLSA-PLUS module
Direction of actionLine-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC40 V DC
28 V AC
Rated current140 mA (25 °C)
Operating effective current ICat UC≤ 5 µA (18x)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Total discharge current Itotal(8/20) µs10 kA
Max. discharge current Imax(8/20) µs5 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 60 V (a, b)
Output voltage limitation at 1 kV/µs (line-earth) static≤ 650 V
Residual voltage at In(line-line)≤ 85 V (a-b)
Residual voltage at In(line-signalground)≤ 85 V
Response time tA(line-line)≤ 1 ns (a-b)
Response time tA(line-earth)≤ 100 ns (a, b)
Input attenuation aE, sym.1.8 dB (Typ. up to 1 MHz / 50 Ω)
0.6 dB (Typ. up to 400 kHz / 150 Ω)
0.2 dB (Typ. up to 60 kHz / 600 Ω)
Input attenuation aE, asym.
Cut-off frequency fg (3 dB), sym. in 50 Ohm system6 MHz (typ.)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system2.5 MHz (typ.)
Cut-off frequency fg (3 dB), sym. in 600 Ohm system750 kHz (typ.)
Capacity (line-earth)1.1 nF (1 MHz a ... b)
Resistance in series22 Ω ±10 %
Surge protection fault messagenone
Max. required back-up fuse145 mA
Impulse durability (line-earth)D1 - 2.5 kA
Impulse durability (signalground-earth)D1 - 2.5 kA

Connection data

Connection methodcan be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection method INCOMTRAB plug-in system
Connection method OUTCOMTRAB plug-in system

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2000

Classifications


ETIM for 2807939 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 24 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.