View larger
PSR-SCP-24UC/URM/5X1/1X2
2981952
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Note on application | |
| Note on application | Only for industrial use |
| Product type | Coupling relay |
| Product family | PSRclassic |
| Application | Safe switch off |
| High demand | |
| Low demand | |
| Mechanical service life | 10x 106cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Data management status | |
| Article revision | 06 |
| Times | |
| Restart time | < 1 s (Boot time) |
| Maximum power dissipation for nominal condition | 8.56 W (at UB= 26.4 V DC, US= 24 V, IS= 47 mA, n = 1, IL² = 72 A², Rcontact= 0.1 ) |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V |
| 250 V | |
| Rated surge voltage/insulation | 4 kV / basic isolation (safe isolation, reinforced isolation and 6 kV between A1/A2, 53/54, 71/72 and 13/14, 23/24, 33/34, 43/44.) |
| General | |
| Rated control circuit supply voltage US | 24 V AC/DC -15 % / +10 % |
| Power consumption at US | typ. 1.2 W |
| Rated control supply current IS | typ. 47 mA |
| Input voltage range | 20.4 V AC/DC ... 26.4 V AC/DC |
| Inrush current | typ. 350 mA DC (Δt s) |
| typ. 350 mA AC (Δt = 2 ms at Us) | |
| Typ. starting time with Us | typ. 20 ms (when controlled via A1) |
| Typical release time | typ. 20 ms (when controlled via A1) |
| Recovery time | < 500 ms |
| Maximum switching frequency | 0.5 Hz |
| Protective circuit | Surge protection; Varistor |
| Operating voltage display | 1 x green LED |
| Contact switching type | 5 enabling current paths |
| 1 confirmation current path | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A (N/O contact) |
| 6 A (N/C contact) | |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2 |
| Interrupting rating (ohmic load) max. | 144 W (N/O contact, 24 V DC, τ = 0 ms) |
| 288 W (N/O contact, 48 V DC, τ = 0 ms) | |
| 240 W (N/O contact, 60 V DC, τ = 0 ms) | |
| 110 W (N/O contact, 110 V DC, τ = 0 ms) | |
| 88 W (N/O contact, 220 V DC, τ = 0 ms) | |
| 1380 VA (N/O contact, 230 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (N/O contact, 24 V DC, τ = 40 ms) |
| 42 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (24 V (DC13)) |
| 3 A (230 V (AC 15)) | |
| Switching capacity (360/h cycles) | 4 A (24 V (DC13)) |
| 4 A (230 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Screw connection |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Tightening torque | 0.6 Nm |
| Width | 22.5 mm |
| Height | 114.5 mm |
| Depth | 99 mm |
| Color (Housing) | yellow (RAL 1018) |
| Housing material | Polyamide |
| Safety data | |
| Stop category | 0 |
| Safety data: EN ISO 13849 | |
| Category | 1 |
| Performance level (PL) | c |
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 1 |
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 1 |
| Safety data | |
| Safety Integrity Level (SIL) | 1 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -20 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | max. 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.) |
| CE | |
| Certificate | CE-compliant |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | DIN EN 50178 |
| Mounting type | DIN rail mounting |
| Mounting position | vertical or horizontal |
| Feature Name | Feature Value |
|---|---|
| Model (EF000010) | Basic device |
| Suitable for rail mounting (EF003972) | Yes |
| With detachable clamps (EF003340) | Yes |
| Type of electric connection (EF003961) | Screw connection |
| Suitable for monitoring of emergency-stop circuits (EF007268) | No |
| Suitable for monitoring of valves (EF007272) | No |
| Suitable for monitoring of optoelectronic protection equipment (EF007269) | No |
| Suitable for monitoring of tactile sensors (EF007271) | No |
| Suitable for monitoring of magnetic switches (EF007266) | No |
| Suitable for monitoring of proximity switches (EF007267) | No |
| Evaluation inputs (EF008245) | Other |
| With start input (EF003342) | No |
| With muting function (EF004057) | No |
| With feedback circuit (EF003343) | No |
| Release-delay (EF001129) | 0.02 s |
| Number of outputs, safety related, undelayed, with contact (EF003344) | 0 |
| Number of outputs, safety related, delayed, with contact (EF003345) | 0 |
| Number of outputs, safety related, undelayed, semiconductors (EF003346) | 0 |
| Number of outputs, safety related, delayed, semiconductors (EF003347) | 0 |
| Number of outputs, signalling function, undelayed, with contact (EF003348) | 0 |
| Number of outputs, signalling function, delayed, with contact (EF003349) | 0 |
| Number of outputs, signalling function, undelayed, semiconductors (EF003350) | 0 |
| Number of outputs, signalling function, delayed, semiconductors (EF003351) | 0 |
| Stop category according to IEC 60204 (EF007498) | Other |
| With approval for BG BIA (EF004145) | No |
| With approval according to UL (EF001783) | No |
| Width (EF000008) | 22.5 mm |
| Height (EF000040) | 114.5 mm |
| Depth (EF000049) | 99 mm |