View larger
QUINT-ORING/24DC/2X20/1X40
2320186
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2320186 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 261 (C-4-2017) |
| GTIN | 4046356524919 |
| Weight per Piece (excluding packing) | 600.000 g |
| Custom tariff number | 85049091 |
| Country of origin | CN (China) |
| Width | 38 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 41 mm |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | 2000 m |
| Nominal input voltage range | 24 V DC |
|---|---|
| Input voltage range | 18 V DC ... 28 V DC (SELV) |
| Nominal input current | 2x 20 A (-25 °C ... 60 °C) |
| 1x 40 A (-25 °C ... 60 °C) | |
| Maximum input current | 2x 26 A (-25°C ... 40°C) |
| 1x 52 A (-25°C ... 40°C) | |
| 120 A (12 ms, SFB Technology) |
| Nominal output voltage | 0.2 V (< DC input) |
|---|---|
| Nominal output current (IN) | 40 A (Increasing power) |
| 20 A (Redundancy) | |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in series | No |
| Output overvoltage protection | ≤ 32 V DC |
| Power loss nominal load max. | 8 W (IOUT= 40 A) |
| Net weight | 0.6 kg |
|---|---|
| Efficiency | > 98 % |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| > 720000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 10 |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 10 mm |
| Screw thread | M3 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| ATEX | II 3 G Ex nA IIC T4 Gc |
| DEKRA 11ATEX0031 X | |
| IECEx | Ex nA IIC T4 Gc |
| IECEx DEK 11.0015X |
| Feature Name | Feature Value |
|---|---|
| Function (EF000030) | Other |
| Voltage type (operating voltage) (EF005294) | DC |
| Operating voltage DC (EF008208) | 18 V |
| With LED indication (EF005950) | Yes |