View larger
PSI-REP-PROFIBUS/12MB
2708863
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2708863 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 318 (C-6-2017) |
| GTIN | 4046356078993 |
| Weight per Piece (excluding packing) | 212.400 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 30 % ... 95 % (non-condensing) |
| Altitude | ≤ 5000 m (For restrictions see manufacturer's declaration) |
| ≤ 2000 m (When used in EX zone 2) | |
| Degree of protection | IP20 |
| Noise immunity | EN 61000-4-2 |
| Transmission channels | 2 (1/1), TD, RD, half duplex |
|---|---|
| Bit delay | 1 bit (Direct mode) |
| Bit distortion, input | max. ± 35 % |
| Bit distortion, output | < 6.25 % |
| Electrical isolation | VCC // TBUS // PROFIBUS (A) // PROFIBUS (B) |
| Test voltage data interfaces | 1.5 kV |
| Test voltage data interface/power supply | 1.5 kVrms(50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise emission | EN 55011 |
| Net weight | 212.4 g |
| Housing material | PA 6.6-FR |
| Color | green |
| MTBF | 1136 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 238 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| MTTF | 1638 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
| 812 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25 % (5 days a week, 12 hours a day)) | |
| 340 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) | |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC IIC T4 Gc X (Please follow the special installation instructions in the documentation!) |
| UL, USA/Canada | cULus listed UL 508 |
| Class I, Zone 2, AEx nA nC IIC T6 | |
| Class I, Zone 2, Ex nA nC IIC T6 Gc X | |
| Class I, Div. 2, Groups A, B, C, D |
| Nominal supply voltage | 24 V DC (With UL approval) |
|---|---|
| Supply voltage range | 18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block) |
| Typical current consumption | < 90 mA (24 V DC) |
| Interface 1 | PROFIBUS acc. to IEC 61158, RS-485 2-conductor |
|---|---|
| Operating mode | Through PROFIBUS connector |
| Connection method | D-SUB-9 female connector |
| File format/coding | UART (11 Bit, NRZ) |
| Data direction switching | Automatic control, min. station response time 2 bits |
| Transmission medium | 2-wire twisted pair, shielded |
| Transmission length | ≤ 1200 m (Depends on transmission speed and cable type) |
| Termination resistor | external |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Output nominal voltage | 5 V DC ±5 % |
| Output current | 50 mA |
| Output name | Relay output |
|---|---|
| Output description | Alarm output |
| Number of outputs | 1 |
| Maximum switching voltage | 30 V DC (1 A) |
| 65 V DC (0.46 A) | |
| 150 V AC (0.46 A) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Type of test | Free fall in acc. with IEC 60068-2-32 |
| Test result | 1 m |
| Type of test | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 |
| Test result | 5g, 10...150 Hz, 2.5 h, in XYZ direction |
| Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
| Test result | 15g, 11 ms period, half-sine shock pulse |
| Noise emission | EN 55011 |
| Noise immunity | EN 61000-4-2 |
| Free from substances that could impair the application of coating | according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 3 GHz |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-5 |
| Signal | ± 1 kV |
| Standards/regulations | EN 55011 |
| EN 61000-4-6 | |
| Designation | Air clearances and creepage distances |
| Standards/regulations | DIN EN 50178, DIN EN 60950 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC IIC T4 Gc X |
| UL, USA/Canada | cULus listed UL 508 |
| Class I, Zone 2, AEx nA nC IIC T6 | |
| Class I, Zone 2, Ex nA nC IIC T6 Gc X | |
| Class I, Div. 2, Groups A, B, C, D | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 |
| Number of interfaces PROFINET (EF006932) | 0 |
| Number of HW-interfaces RS-232 (EF003021) | 0 |
| Number of HW-interfaces RS-422 (EF003022) | 0 |
| Number of HW-interfaces RS-485 (EF003023) | 0 |
| Number of HW-interfaces serial TTY (EF003024) | 0 |
| Number of HW-interfaces USB (EF003025) | 0 |
| Number of HW-interfaces parallel (EF003026) | 0 |
| Number of HW-interfaces wireless (EF006933) | 0 |
| Number of HW-interfaces other (EF003027) | 0 |
| With optical interface (EF003028) | No |
| Supporting protocol for EtherCAT (EF017564) | No |
| Supporting protocol for TCP/IP (EF003050) | No |
| Supporting protocol for PROFIBUS (EF003052) | Yes |
| Supporting protocol for CAN (EF003053) | No |
| Supporting protocol for INTERBUS (EF003054) | No |
| Supporting protocol for ASI (EF003051) | No |
| Supporting protocol for KNX (EF003055) | No |
| Supporting protocol for Modbus (EF003057) | No |
| Supporting protocol for Data-Highway (EF003058) | No |
| Supporting protocol for DeviceNet (EF003059) | No |
| Supporting protocol for SUCONET (EF003060) | No |
| Supporting protocol for LON (EF003017) | No |
| Supporting protocol for PROFINET IO (EF007525) | No |
| Supporting protocol for PROFINET CBA (EF007524) | No |
| Supporting protocol for SERCOS (EF006657) | No |
| Supporting protocol for Foundation Fieldbus (EF007522) | No |
| Supporting protocol for EtherNet/IP (EF007521) | No |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | No |
| Supporting protocol for DeviceNet Safety (EF007520) | No |
| Supporting protocol for INTERBUS-Safety (EF006662) | No |
| Supporting protocol for PROFIsafe (EF007526) | No |
| Supporting protocol for SafetyBUS p (EF007527) | No |
| Supporting protocol for other bus systems (EF003062) | No |
| Radio standard Bluetooth (EF007178) | No |
| Radio standard WLAN 802.11 (EF007179) | No |
| Radio standard GPRS (EF008523) | No |
| Radio standard GSM (EF008524) | No |
| Radio standard UMTS (EF008525) | No |
| IO link master (EF007298) | No |
| Redundancy (EF003156) | No |
| With potential separation (EF003272) | No |
| SIL according to IEC 61508 (EF009889) | None |
| Suitable for safety functions (EF001597) | No |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Appendant operation agent (Ex ia) (EF004141) | No |
| Appendant operation agent (Ex ib) (EF004142) | No |
| Explosion safety category for gas (EF003997) | None |
| Explosion safety category for dust (EF003998) | None |
| Width (EF000008) | 35 mm |
| Height (EF000040) | 99 mm |
| Depth (EF000049) | 105 mm |