View larger
MACX MCR-EX-T-UI-UP
2865654
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2865654 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 148 (C-5-2017) |
| GTIN | 4046356296670 |
| Weight per Piece (excluding packing) | 168.800 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | typ. 5 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 5g, accordance to IEC 60068-2-6 |
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
|---|---|
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Input signal range | 0 Ω ... 50 kΩ |
| Potentiometer resistance range | 0 Ω ... 50 kΩ |
| Input signal range | -1000 mV ... 1000 mV |
| Configurable/programmable | Yes |
|---|---|
| Max. voltage output signal | ± 11 V |
| Current output signal | 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL) |
| Max. current output signal | 22 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | ≤ 600 Ω (20 mA) |
| Behavior in the event of a sensor error | according to NE 43 or freely configurable |
| Output name | Switching output |
| Configurable/programmable | Yes |
| Contact type | 1 PDT |
| Contact material | AgSnO2, hard gold-plated |
| Maximum switching voltage | 30 V AC (30 V DC) |
| Maximum inrush current | 0.5 A (30 V AC) |
| 1 A (30 V DC) | |
| Mechanical service life | 1x 105cycles |
| Supply voltage range | 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz) |
|---|---|
| Typical current consumption | < 50 mA (24 V DC) |
| Power consumption | < 1.5 W |
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Connection method | Screw connection |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Maximum transmission error | 0.1 % (E.g., at Pt 100, 300 K min. span) |
|---|---|
| Maximum temperature coefficient | 0.01 %/K |
| Step response (0–99%) | typ. 1000 ms (With SIL) |
| typ. 700 ms (Without SIL) | |
| Status display | Green LED (supply voltage, PWR) |
| Red LED, flashing (line, sensor error, ERR) | |
| Red LED (module error, ERR) | |
| Yellow LED (switching output) | |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Input/output/power supply |
| Electrical isolation | 2.5 kV (50 Hz, 1 min., test voltage) |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/power supply |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/switching output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Output/supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| Conformance | CE-compliant |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 G Ex nA nC ic IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA nC ic IIC T4 Gc X | |
| UL, USA/Canada | UL 508 Listed |
| SIL | 2 |
| Max. internal inductance Li | negligible |
|---|---|
| Max. internal capacitance Ci | 44 nF |
| Max. output voltage Uo | 6 V |
| Max. output current Io | 7.4 mA |
| Max. output power Po | 11 mW |
| Group | IIC |
| Max. external inductivity Lo | 100 mH |
| Max. external capacity Co | 1.3 µF |
| Group | IIC |
| Max. external inductivity Lo | 10 mH |
| Max. external capacity Co | 1.7 µF |
| Group | IIC |
| Max. external inductivity Lo | 1 mH |
| Max. external capacity Co | 2.6 µF |
| Group | IIB |
| Max. external inductivity Lo | 100 mH |
| Max. external capacity Co | 6.8 µF |
| Group | IIB |
| Max. external inductivity Lo | 10 mH |
| Max. external capacity Co | 9.2 µF |
| Group | IIB |
| Max. external inductivity Lo | 1 mH |
| Max. external capacity Co | 15 µF |
| Safety-related maximum voltage Um | 253 V AC/DC |
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 2 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 2 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 2 % |
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | 4-way, between input/output/power supply/switching output |
| Flammability rating according to UL 94 | V0 |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 5g, accordance to IEC 60068-2-6 |
| Conformance | CE-compliant |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 G Ex nA nC ic IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA nC ic IIC T4 Gc X | |
| UL, USA/Canada | UL 508 Listed |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIC | |
| IIC | |
| IIB | |
| IIB | |
| IIB |
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Measuring range (EF001836) | -250 °C |
| Analogue output 0 mA ... 20 mA (EF006808) | No |
| Analogue output 4 mA ... 20 mA (EF006810) | Yes |
| Analogue output 0 V ... 2 V (EF009886) | No |
| Analogue output 0 V ... 5 V (EF009887) | No |
| Analogue output 0 V ... 10 V (EF006807) | No |
| Analogue output 2 V ... 10 V (EF009888) | No |
| With switching output (EF005225) | Yes |
| EMC-version (EF001062) | Yes |
| Ambient temperature (EF002386) | 65 °C |
| Weight (EF000167) | 0.2641 kg |