PHOENIX CONTACT PT-IQ-PTB-UT PT-IQ-PTB-UT 2800768 PHOENIX CONTACT Supply and remote module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT-IQ-PTB-UT 2800768 PHOENIX CONTACT Supply and remote module

PT-IQ-PTB-UT

2800768

PHOENIX CONTACT

1 Pcs.

Supply and remote module Module for potential-free multi-level remote power supply and indication of connected surge protection modules.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2800768
Packing unit1 pc
Catalog pagePage 96 (C-4-2017)
GTIN4046356647984
Weight per Piece (excluding packing)78.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height91.1 mm
Width17.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible

Additional descriptions

NoteRemote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Protective circuit

Surge protection fault messageOptical, multi-stage remote indication contact

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Connection, equipotential bonding

Connection methodDIN rail NS35

Remote indication contact

Switching function2x N/C contacts
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 14

Supply status indicator / remote signaling

Operating voltage20 V DC ... 30 V DC
Rated currentmax. 130 mA (24 V DC)
max. 160 mA (20 V DC)
Max. required back-up fuse500 mA (T)
Number of surge protection modules that can be mounted side by side28 (32 °C)

Standards and Regulations

Standards/specificationsEN 61000-6-2 2005
EN 61000-6-3 2007 + A1:2011
EN 60950-1 2006 + A2:2013
EN 60079-0 2012
EN 60079-11 2012
EN 60079-15 2010
EN 60079-26 2007
IEC 60079-0 2011 (modified) + corrigendum 2012
IEC 60079-11 2011 + Corrigendum 2012
IEC 60079-15 2010
IEC 60079-26 2006

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.