PHOENIX CONTACT CN-LAMBDA/4-2.25-BB CN-LAMBDA/4-2.25-BB 2801057 PHOENIX CONTACT Attachment plug with Lambda/4 technology as surge protection for.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CN-LAMBDA/4-2.25-BB 2801057 PHOENIX CONTACT Attachment plug with Lambda/4 technology as surge protection for..

CN-LAMBDA/4-2.25-BB

2801057

PHOENIX CONTACT

1 Pcs.

Attachment plug with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N connectors socket-socket Adapter with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N Female-Female Connectors

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Dimensions

Height78.7 mm
Width25 mm
Depth77.5 mm
Length77.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP68

General

Housing materialHPb59-1
Colornickel
Standards for cearances and creepage distancesIEC 60664-1
Mounting typeConnection-specific intermediate plugging
TypeAttachment plug
Number of positions1
Direction of actionLine-Shield/Earth Ground

Protective circuit

IEC test classificationC2
C3
D1
Nominal current IN5 A (25 °C)
Nominal discharge current In(8/20) µs50 kA
Nominal discharge current In(8/20) µs (Core-Earth)50 kA
Nominal discharge current In(8/20) µs (Core-Shield)50 kA
Total surge current (8/20) µs60 kA
Total surge current (10/350) µs20 kA
Max. discharge current Imax(8/20) µs60 kA
Max. discharge current Imax(8/20) µs maximum (Core-Earth)60 kA
Max. discharge current Imax(8/20) µs maximum (Core-Shield)60 kA
Impulse discharge current (10/350)˽µs, peak value limp20 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 1 V
Output voltage limitation at 1 kV/µs (Core-Shield) spike≤ 1 V
Voltage protection level Up(core-ground)≤ 25 V (C2 - 10 kV / 5 kA)
≤ 5 V (C1 - 1 kV/500 A)
≤ 18 V (6 kV/3 kA)
Voltage protection level Up(core-shield)≤ 5 V (C1 - 1 kV/500 A)
≤ 25 V (C2 - 10 kV / 5 kA)
≤ 18 V (6 kV/3 kA)
Input attenuation aE, asym.typ. 0.1 dB
Frequency range0.8 GHz ... 2.25 GHz
Standing wave ratio SWR in a 50 Ω systemtyp. 1.2
max. 1.25
Permissible HF power Pmaxat VSWR = xx (50 ohm system)≤ 500 W
≤ 4 kW (peak)
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
D1 - 2,5 kA

Connection data

Connection methodN connector 50 Ω
Connection type INN connector, female
Connection type OUTN connector, female

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.