View larger
REL-FO/LRC-230AC/1X21/MS
1308323
PHOENIX CONTACT
10 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| General | They should not be used to separate SELV/PELV electrical circuits from other electrical circuits, as safe separation is not guaranteed. (valid for optocoupler variants) |
| General | Protection against accidental contact of the article (with voltages > 25 V AC/60 V DC) must be ensured by the system manufacturer. This is an assembly device without protection against direct contact. |
| Product Type | Individual relay |
| Product Family | ESSENTIAL edition |
| Operating Mode | Working time 100% |
| Mechanical service life | approx. 3x 107operations |
| Relay Type | Electromechanical relay |
| Insulation Properties: Leak Lines and Air Gaps Between Circuits | |
| Isolation | Basic Insulation |
| Surge Category | Ii |
| Degree of pollution | 3 |
| Maximum Dissipated Power with Nominal Condition | 1 W |
| Test Voltage (Winding/Contact) | 5 kVEff(50 Hz, 1 min., winding/contact) |
| Test Voltage () | 1 kVEff(50 Hz, 1 min., open contact) |
| Creepage lines and air gaps between circuits | |
| Sizing Insulation Voltage | 250 V AC |
| Dimensioning Transient Voltage | 2.5 kV |
| Arousal Side | |
| Nominal Input Voltage UN | 230 V AC |
| Input Voltage Range | 184 V AC ... 253 V AC |
| Mains Frequency | 50/60 Hz |
| Drive switching behavior | monostable |
| Drive (polarity) | bipolar |
| Typical Input Current to UN | 4.5 mA (50 Hz) |
| Input Dissipated Power with UN | 1 W |
| Typical Reaction Time | 2 ms ... 15 ms |
| Typical Open Time Range | 5 ms ... 20 ms |
| Protection Circuit | RC Module |
| Status Indication | Yellow LED |
| Coil Resistance | 24100 Ω ±10 % |
| Commute | |
| Contact Switching Type | 1 switch |
| Switching Contact Type | Simple Contact |
| Contact Material | AgSnO |
| Maximum Switching Voltage | 250 V AC/DC |
| Minimum Activation Voltage | 5 V (100 mA) |
| Constant Current Limit | 12 A |
| Maximum connection current | 24 A (20 ms, open contact) |
| Minimum Shut-Off Current | 100 mA (5 V) |
| Maximum Breaking Power (Ohmic Load) | 288 W (24 V DC) |
| 360 W (30 V DC) | |
| 3000 VA (250 V AC) | |
| Connection type | FASTON Connection |
| Width | 13 mm |
| Height | 31.1 mm |
| Depth | 35 mm |
| Environmental conditions | |
| Protection Index (Relay) | RT II (Relay) |
| Protection Index (Installation Location) | IP54 (Mounting Location) |
| Ambient Temperature (Service) | -40 °C ... 70 °C |
| Ambient Temperature (Storage/Transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Standards/Specifications | IEC 61810-1 |
| IEC 60664-1 | |
| Creepage lines and air gaps between circuits | |
| Standards/Specifications | IEC 60664-1 |
| Position for mounting | discretionary |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Plug-in connection |
| Complete with socket (EF003359) | No |
| With detachable clamps (EF003340) | No |
| With LED indication (EF005950) | Yes |
| Rated control supply voltage AC 50 Hz (EF003978) | 184 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 184 V |
| Voltage type for actuating (EF008242) | AC |
| Drive, polarization (EF003355) | Polarity free |
| Drive, switching attitude (EF003356) | Mono stable |
| Number of contacts as normally closed contact (EF008255) | 0 |
| Number of contacts as normally open contact (EF008256) | 0 |
| Number of contacts as change-over contact (EF008257) | 1 |
| Type of switch contact (EF003358) | Single contact |
| With forced-guided contacts (EF003357) | No |
| Material of contact insert (EF008521) | Other |
| Material of contact surface (EF004020) | Untreated |
| Nominal current (EF000001) | 0.0045 A |
| Degree of protection (IP) (EF005474) | Other |
| Width (EF000008) | 13 mm |
| Height (EF000040) | 31.1 mm |
| Depth (EF000049) | 35 mm |