LEGRAND 422085 422085 LEGRAND DPX3 630 ELECT. 4P 630A 70kA View larger
Images are for illustrative purposes only. Please refer to data sheet for details

422085 LEGRAND DPX3 630 ELECT. 4P 630A 70kA

422085

422085

LEGRAND

1 Pcs.

DPX3 630 ELECT. 4P 630A 70kA MCCB DPX³ 630 - S2 electronic release - 4P - Icu 70 kA (400 V~) - In 630 A Automatic MCCB DPX³ 630 - electronic S2 - 4P - 70kA - 630A

Automation > Power circuit-breaker for trafo/generator/installation protection
DPX3 MOLDED BOX

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

  • Pack (number of units)1
  • Volume (dm3)10.00
  • Weight (g)7 452.00
Product characteristics
MCCBs electronic release S2 - fixed version
  • Adjustment of Ir, Isd, tr, tsd
  • Instantaneous protection If = 5 kA
  • Green indicator lamp
  • Connector for test unit
  • Logic and dynamic selectivity
  • 4P version: adjustment of neutral on front panel
Breaking capacity Icu 70 kA (400 V~)
  • 4P
  • In : 630 A
General characteristics
DPX³ 630 - S2 electronic release MCCBs from 250 to 630 A
  • Moulded case MCCBs for switching, control isolation and protection of low voltage electrical lines
  • Can be fitted with auxiliaries
  • Can be used with earth leakage modules or with residual current relays
  • Supplied complete with:
    • fixing screws
    • connection plates for bars
    • insulated shields (phase barriers)
  • Conform to IEC 60947-2 - Sealable adjustment
  • Can be mounted on plate in XL³ cabinets and enclosures

ETIM for 422085 Low-voltage industrial controls and switchgear (EC000228)
Feature Name Feature Value
Degree of protection (IP) (EF005474) IP30
Number of auxiliary contacts as change-over contact (EF003531) 2
Adjustment range undelayed short-circuit release (EF007131) 5000 A
Integrated earth fault protection (EF007296) No
With integrated under voltage release (EF001390) Yes
Suitable for DIN rail (top hat rail) mounting (EF007250) No
Device construction (EF008240) Built-in device fixed built-in technique
Number of poles (EF001391) 4
Type of electrical connection of main circuit (EF006819) Screw connection
Overload release current setting (EF002336) 252 A
Motor drive integrated (EF006697) No
Adjustment range short-term delayed short-circuit release (EF007129) 378 A
Type of control element (EF006976) Toggle
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) 70 kA
Rated permanent current Iu (EF001389) 630 A
With switched-off indicator (EF007006) Yes
Motor drive optional (EF007386) Yes
Position of connection for main current circuit (EF006671) Front
Rated voltage (EF003977) 220 V
DIN rail (top hat rail) mounting optional (EF008904) No
Complete device with protection unit (EF008906) Yes