LEGRAND 420033 420033 LEGRAND DPX3160 mag+dif 4P 63A 16kA View larger
Images are for illustrative purposes only. Please refer to data sheet for details

420033 LEGRAND DPX3160 mag+dif 4P 63A 16kA

420033

420033

LEGRAND

1 Pcs.

DPX3160 mag+dif 4P 63A 16kA DPX³ 160 4 Pole 63A Thermal Magnetic MCCB with Earth Leakage Module 16kA Automatic MCCB DPX³ 160 - differential circuit breaker - 4P - 16kA - 63A

Automation > Power circuit-breaker for trafo/generator/installation protection
DPX3 MOLDED BOX

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Rated permanent current Iu63 A
Rated voltage220-690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz16 kA
Overload release current setting50.4-63 A
Adjustment range short-term delayed short-circuit release630-630 A
Adjustment range undelayed short-circuit release630-630 A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionYes
Type of electrical connection of main circuitScrew connection
Suitable for DIN rail (top hat rail) mountingYes
DIN rail (top hat rail) mounting optionalYes
Number of auxiliary contacts as normally closed contact1
Number of auxiliary contacts as change-over contact1
With switched-off indicatorYes
With integrated under voltage releaseYes
Number of poles4
Position of connection for main current circuitFront side
Type of control elementWing knob
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
Contains Batteries and/or AccumulatorYes
IEC code (Pack1)CR1616
Battery ou Accumulator (Pack1)Battery (not rechargeable)
Element Composition (Pack1)Lithium (battery or accumulator)
Number of Pack 12
Number of Single Element (Pack1)1
Single Element weight (Pack1)1.1 g
Pack1 LocationProduct includes a battery
Regulation Type (Pack1)P : Portable (Standard format)

ETIM for 420033 Low-voltage industrial controls and switchgear (EC000228)
Feature Name Feature Value
Degree of protection (IP) (EF005474) IP30
Number of auxiliary contacts as change-over contact (EF003531) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Adjustment range undelayed short-circuit release (EF007131) 630 A
Integrated earth fault protection (EF007296) Yes
With integrated under voltage release (EF001390) Yes
Suitable for DIN rail (top hat rail) mounting (EF007250) Yes
Device construction (EF008240) Built-in device fixed built-in technique
Number of poles (EF001391) 4
Type of electrical connection of main circuit (EF006819) Screw connection
Overload release current setting (EF002336) 50.4 A
Motor drive integrated (EF006697) No
Adjustment range short-term delayed short-circuit release (EF007129) 630 A
Type of control element (EF006976) Toggle
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) 16 kA
Rated permanent current Iu (EF001389) 63 A
With switched-off indicator (EF007006) Yes
Motor drive optional (EF007386) Yes
Position of connection for main current circuit (EF006671) Front
Rated voltage (EF003977) 220 V
DIN rail (top hat rail) mounting optional (EF008904) Yes
Complete device with protection unit (EF008906) Yes

Product Datasheet