LAPP 2170240 2170240 UNITRONIC BUS EIB 2x2x0,8 LAPP UNITRONIC BUS EIB 2x2x0,8 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

2170240 UNITRONIC BUS EIB 2x2x0,8 LAPP UNITRONIC BUS EIB 2x2x0,8

2170240

2170240

UNITRONIC BUS EIB 2x2x0,8

LAPP

1 m.

UNITRONIC BUS EIB 2X2X0,8 UNITRONIC® BUS EIB / KNX

Cables > Data and communication cable
UNITRONIC BUS cabling

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Use in building automation for control of lighting, heating, air-conditioning, time management, etc. temperature range from -30°C bis +70°C

  • EIB / European Installation Bus
  • KNX/communication in building management
  • CPR: Article number choice under www.lappkabel.com/cpr

Application range

  • The product is designed for use in building management, e.g. for decentralised control of lighting, heating, air-conditioning, ventilation, energy management, blinds, time management, locking systems etc.
  • The cable can be laid on or under plaster; in pipes, cable ducts; in dry, damp or wet environments.
  • EIB installation mainly consists of sensors/command-transmitters (e.g. light barriers, switches, thermostats, infrared, wind meters, timers), and actuators (e.g. engines, heaters, ventilators, lights, blinds).
  • KNX technology was formed from the merging of three established European bus standards: EIP, EHS (household appliances and consumer electronics) and Batibus (heating/ventilation/air conditioning)

Product features

  • Serial data transmission
  • EIB cable has been tested at 4 kV (1 min.) in a water bath

Product Make-up

  • Screened installation cable based on type J-Y(ST)Y according to DIN VDE 0815
  • UNITRONIC® BUS EIB
    Bare solid copper wire
    2x2x0,8: red and black, white and yellow
    Core insulation: PVC
    Overall aluminum foil
    Outer sheath: PVC, green (RAL 6017)
  • UNITRONIC® BUS EIBCOMBI
    Bare solid copper wire
    Core insulation: PVC
    2x2x0,8: red und black, white and yellow
    3x1,5: brown, blue, green/yellow
    Overall aluminum foil
    Outer sheath: PVC, green (RAL 6017)

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000830
  • ETIM 5.0 Class-Description: Data cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000830
  • ETIM 6.0 Class-Description: Data cable

Mutual capacitance

  • (800 Hz) max. 100 nF/km

Peak operating voltage

  • (not for power applications) 250 V

Conductor resistance

  • (loop): max. 73.2 ohm/km

Minimum bending radius

  • Fixed installation:
    5 x outer diameter

Test voltage

  • Core/core: 4000 V

Temperature range

  • Fixed installation: -30°C to +70°C

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.