LAPP 1708004 1708004 LAPP (J)-Y(ST)Y... LG 4X2X0.8 BMK View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1708004 LAPP (J)-Y(ST)Y... LG 4X2X0.8 BMK

1708004

1708004

LAPP

100 m.

(J)-Y(ST)Y...LG 4X2X0,8 BMK Fire alarm cable (J)-Y(ST)Y... LG

Connectors > Printed circuit board connector
UNITRONIC low frequency

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

(J)-Y(ST)Y... LG, layered braided PVC fire alarm cable with red cover for fixed installation and foil shielding, installation, e.g. over or under plaster

proceeds

  • The cable is marked with the phrase "Fire alarm cable" at regular intervals on the cover. Therefore, it is used especially for installation in fire alarm systems.
  • Aluminum tape display and drain wire minimize high-frequency interference in electromagnetic fields
  • Decoupling of electrical circuits by structure in twisted pairs (crosstalk effects)

Scope of use

  • Signal transmissions
  • For fixed or low gymp installation, in dry and wet interiors
  • For outdoor use this cable should be installed only under a sydy

Product features

  • The 2-pair version (2 x 2 x 0.8) is twisted into a star-square shaped
  • Non-flame propagator, according to IEC 60332-1-2

Product composition

  • Bare solid copper conductor
  • Conductor insulation made of PVC
  • Conductors braided in pairs,
    twisted pairs together,
    General aluminum tape display with copper drain wire
  • Outer cover made of PVC
    Outer shell color: fire red (RAL 3000)

ETS Classification 5

  • ETIM 5.0 Class-ID: EC000829
  • ETIM Class 5.0 Description: Signal/Telecommunications Cable

ETTIM Rating 6

  • ETIM 6.0 Class-ID: EC000829
  • ETIM 6.0 Class-Description: Telecommunication cable

Driver Identification Code

  • According to VDE 0815 (Appendix T10)

Coupling

  • (800 Hz): K1: 80% ≤ 300 pF/100m

Driver cross section in

  • 0.8 mm: 0.50 mm²

Cable attenuation / attenuation

  • 0.8 mm: 1.1 dB/km

Minimum radius of curvature

  • Fixed installation: 10 x outer diameter

Test voltage

  • Driver/conductor: 800 V
  • Driver/display: 800 V

Loop resistance

  • max. 73.2 Ohm/km

Temperature range

  • Occasional flexible use: –5°C to +50°C
  • Fixed installation: -30°C to +70°C

Product Datasheet