According to VDE 0100-711, cables with low smoke emission are required in buildings for exhibitions, shows and stands without a fire alarm system
Type-compliant versions <HAR>-certified with "<HAR>” testing and certification mark for accelerated granting of approvals if final application of cable is within the European CENELEC area
Application range
Stage technology
For mobile equipment and machines
According to EN 50565-2: In dry, damp and wet rooms as well as for fixed installation e.g. on the plaster
For buildings or industrial plants with a high density of people or valuable assets
Product features
Low amount of corrosive gases in the event of fire
Flame-retardant according to IEC 60332-1-2 and bundle flame test according to IEC 60332-3-24
Low smokes/low smoke density in the event of fire according to IEC 61034
Ozone-resistant acc. to EN 50363-6, EN 60811-403, EN 50396-8.1.3
Norm references / Approvals
<HAR> H07ZZ-F cable type approval according to EN 50525-3-21
Product Make-up
Conductor made of bare copper wires
Core insulation: rubber compound, halogen-free
Outer sheath: rubber compound, halogen-free
Classification ETIM 5
ETIM 5.0 Class-ID: EC001578
ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6
ETIM 6.0 Class-ID: EC001578
ETIM 6.0 Class-Description: Flexible cable
Core identification code
Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9
From 6 cores: black with white numbers
Conductor stranding
Fine wire according to VDE 0295 Class 5/ IEC 60228 Class 5
Minimum bending radius
4 to 8 x outer diameter (EN 50565-1)
Nominal voltage
U0/U: 450/750 VAC In protected and fixed installations: U0/U: 600/1000 V
Test voltage
2500 V
Protective conductor
G = with GN-YE protective conductor
X = without protective conductor
Current rating
VDE 0298 Part 4
EN 50565-1/ VDE 0298-565-1
Temperature range
Fixed installation: -40°C up to +90°C
Occasionally moved: -5°C up to +90°C
Product Datasheet