EATON - MOELLER NZM3-4-XSVS NZM3-4-XSVS 168473 Y7-168473 EATON ELECTRIC 168473 NZM3-4-XSVS View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZM3-4-XSVS 168473 Y7-168473 EATON ELECTRIC 168473 NZM3-4-XSVS

NZM3-4-XSVS

168473

Y7-168473

EATON - MOELLER

1 Pcs.

168473 NZM3-4-XSVS NZM3-4-XSVS Socket, 4p, 630A Optional accessories for circuit-breaker series NZM offers a comprehensive portfolio of application possibilities for worldwide use. Modular functional groups make mounting flexible and simple.

Automation > Chassis part power circuit breaker
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Socket, 4p, 630A
Optional accessories for circuit-breaker series NZM offers a comprehensive portfolio of application possibilities for worldwide use. Modular functional groups make mounting flexible and simple.

General specifications
Product name
Eaton Moeller series NZM plug-in unit
Part no.
NZM3-4-XSVS
EAN
4015081649549
Product Length/Depth
345 millimetre
Product height
132 millimetre
Product width
185 millimetre
Product weight
3.66 kilogram
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947
Product Tradename
NZM
Product Type
Accessories
Product Sub Type
Plug-in unit
Delivery program
Type
AccessoryPlug-in socket for basic unit
Number of poles
Four-pole
Nominal current
500 A
Features
Version as built-in device
Frame
NZM3
Technical Data - Electrical
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Direction of incoming supply
As required
Technical Data - Mechanical
Mounting Method
Plug-in unit
Mounting position
Vertical and 90° right/left
Degree of protection
IP2X (in the area of the plug-in area)
Protection against direct contact
Finger and back-of-hand proof to VDE 0106 part 100
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Technical Data - Mechanical - Terminals
Terminal equipment included
Screw connection
Design verification as per IEC/EN 61439 - technical data
Equipment heat dissipation, current-dependent
83.35 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Chassis part power circuit breaker (EC002043)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Chassis part circuit breaker (ecl@ss13-27-37-04-22 [ACN955016])
Rated current In
500 A
Number of poles
4
Version as busbar adapter
No
Version as built-in device
Yes
Type of electrical connection of main circuit
Screw connection

ETIM for 168473 Low-voltage industrial controls and switchgear (EC002043)
Feature Name Feature Value
Rated current In (EF008250) 500 A
Number of poles (EF001391) 4
Version as busbar adapter (EF006965) No
Version as built-in device (EF006954) Yes
Type of electrical connection of main circuit (EF006819) Screw connection

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.