EATON - MOELLER IZMX-ST24DC-1 IZMX-ST24DC-1 184266 Y7-184266 EATON ELECTRIC Shunt release 24 VDC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

IZMX-ST24DC-1 184266 Y7-184266 EATON ELECTRIC Shunt release 24 VDC

IZMX-ST24DC-1

184266

Y7-184266

EATON - MOELLER

1 Pcs.

Shunt release 24 VDC IZMX-ST24DC-1 Eaton Moeller series IZMX/INX - ACB. Shunt release 24 VDC, 1 Accessories, Shunt release (for power circuit breaker), Can be combined with an undervoltage release or a second shunt release., Retrofitting kit, Maximum operating frequency Actuations/minute 3, Limited to 3/min due to the high pick-up current for 35 ms., Please note - the circuit-breaker's switching frequency = 60/h, Rated control voltage Us 24 V DC V, Operating range x US 0,7 - 1,1 Factor, max. holding current In 0.18 A, max. pick-up current (35ms) In 19 A, max. continuous power AC/DC 5 VA/W, max. pull-in power (35ms) AC/DC 500 VA/W, Circuit-breaker total switching time @ US=100% 30 (IZMX16…, INX16…), 35 (IZMX40…, INX40…) ms , For use with IZMX16..., IZMX40..., INX16..., INX40...

Automation > Shunt release (for power circuit breaker)
Circuit Breakers IZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series IZMX/INX shunt release
Catalog Number
184266
Model Code
IZMX-ST24DC-1
EAN
4015081784189
Product Length/Depth
150 mm
Product Height
100 mm
Product Width
100 mm
Product Weight
0.113 kg
Compliances
RoHS conform

Delivery program

Type
Accessory
Accessory/spare part type
Remote switching

Technical data - electrical

Voltage type
DC
Control voltage operating range
0.7 - 1.1 x Us
24 V DC
Rated control supply voltage (Us) at AC, 50 Hz - min
0 V
Rated control supply voltage (Us) at AC, 50 Hz - max
0 V
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Rated control supply voltage (Us) at DC - min
24 V
Rated control supply voltage (Us) at DC - max
24 V
Current rating - max
0.18 A (maximum holding current)
Rated operational current
0.18 A (maximum holding current)
Starting current rating
19 A (35 ms)
Adjustment range undelayed short-circuit release (end value) - max
0 A
Power consumption
5 VA/W AC/DC
Pick-up power consumption at 35 ms - max
500 VA/W
Circuit breaker total switching time
30 ms (Us = 100%) (IZMX16…, INX16…)
35 ms (Us = 100%) (IZMX40…, INX40…)
Initial value of the undelayed short-circuit release - min
0 A

Technical data - mechanical

Number of actuation per minute - max
3
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C

Additional information

Special features
Suitable for
Off-load switch
Power circuit breaker
Overload relay
Used with
INX16..., INX40...
IZMX16..., IZMX40...

ETIM for 184266 Low-voltage industrial controls and switchgear (EC001023)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 0 V
Rated control supply voltage AC 60 Hz (EF003979) 0 V
Rated control supply voltage DC (EF003980) 24 V
Voltage type for actuating (EF008242) DC
Initial value of the undelayed short-circuit release - setting range (EF008187) 0 A
End value adjustment range undelayed short-circuit release (EF008188) 0 A
Power consumption (EF000346) 5 W
Type of electric connection (EF003961) Flat plug-in connection
Number of contacts as normally open contact (EF008256) 0
Number of contacts as normally closed contact (EF008255) 0
Number of contacts as change-over contact (EF008257) 0
Suitable for power circuit breaker (EF005863) Yes
Suitable for off-load switch (EF001543) Yes
Suitable for motor safety switch (EF005826) No
Suitable for overload relay (EF001545) Yes

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.