EATON - MOELLER NZM1-XFI30U NZM1-XFI30U 104609 Y7-104609 EATON ELECTRIC Earth-fault release, 30mA, 3p, bottom View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZM1-XFI30U 104609 Y7-104609 EATON ELECTRIC Earth-fault release, 30mA, 3p, bottom

NZM1-XFI30U

104609

Y7-104609

EATON - MOELLER

1 Pcs.

Earth-fault release, 30mA, 3p, bottom NZM1-XFI30U Eaton Moeller series NZM - Molded Case Circuit Breaker. Earth-fault release, 30mA, 3p, bottom Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: approved according to IEC/EN 60947-2 not UL/CSA approved. Suitable for use in three- and single-phase systems. Pulse current sensitive according to core-balance principle. For 3 and 4 pole NZM1(-4) circuit-breakers and switch-disconnectors N1(-4).mains voltage independent Ue = 200 .. 415 V 50/60 Hz. At I △n = 0.03 A: delay time t v always fixed setting to 10 ms. Warning message > 30 % I △n by yellow LED . Trip indication max. 2 auxiliary contacts (HIAFI) can be fitted by user: N/O = M22-K01, N/C = M22-K10 are reset via the reset button. If the trip-indicating auxiliary co

Automation > Residual current release for power circuit breaker
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series NZM release
Catalog Number
104609
Model Code
NZM1-XFI30U
EAN
4015081044191
Product Length/Depth
180 mm
Product Height
80 mm
Product Width
90 mm
Product Weight
0.9 kg
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947-2
IEC/EN 60947-2 annex B

Product specifications

Type
AccessoryEarth-fault releases
Special features
Earth-fault release to IEC/EN 60947-2Not UL/CSA approvedSuitable for use in three-phase systemsPulse-current sensitive type A according to core-balance principleFor 3 pole NZM1 circuit-breakers and N1 switch-disconnectorsSupply voltage-dependent Ue = 200 – 415 V 50/60 HzControl knobs, sealable.Bottom mounting up to 100 A
Application
In three-phase systems
Voltage rating
200 - 415 V AC, min. 80 V AC for detection of fault currents type A/AC (dependent on mains voltage)
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Frame
NZM1
45 mm
Frequency rating
50 Hz / 60 Hz
Used with
NZM1
Three-pole
N(S)1
Mounting Method
Bottom
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-5 °C
Current rating - max
100 A
Power on-delay time - max
30 ms
Power on-delay time - min
30 ms
Rated control supply voltage (Us) at AC, 50 Hz - max
415 V
Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
415 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Degree of protection
IP20 (operating component area)
Mounting position
Vertical and 90° in all directions
Lifespan, mechanical
20000 operations
Fault current detection range
50/60 Hz
Number of poles
Three-pole
Terminal capacity (solid/flexible conductor)
As NZM1 standard terminal with ferrules
As NZM1 standard terminal without ferrules
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Rated control supply voltage (Us) at DC - min
0 V
Rated fault current - max
0.03 A
Rated fault current - min
0.03 A
Rated operating voltage (Ue) - max
415 V
Sensitivity type
Pulse-current sensitive as per core-balance principle (type A)

ETIM for 104609 Low-voltage industrial controls and switchgear (EC001021)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 200 V
Rated control supply voltage AC 60 Hz (EF003979) 200 V
Rated control supply voltage DC (EF003980) 0 V
Rated fault current (EF003975) 0.03 A
Max. power on-delay time (EF008259) 30 ms
Delay adjustable (EF001420) No
Max. rated operation voltage Ue (EF007357) 415 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.