ABB 1SDA068111R1 1SDA068111R1 ABB XT4N 250 TMA 250-2500 4p F F InN 100% View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA068111R1 ABB XT4N 250 TMA 250-2500 4p F F InN 100%

1SDA068111R1

068111

ABB

1 Pcs.

XT4N 250 TMA 250-2500 4p F F InN=100% XT4N250 TMA R250 Im2500 4P F F

Automation > Power circuit-breaker for trafo/generator/installation protection
Molded Case Circuit Breakers ≤ 250 A Xtmax

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ABB EcoSolutions
ABB EcoSolutionsYes
Circular Value
Circular Design Principles Recyclability RateDesign for Closing Resource Loops - Standard EN45555 - 56.3 %
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
End of Life Instructions9AKK108468A2351
Group Waste to Landfill TargetUL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA9AKK108467A8326
Eco Transparency
Environmental Product Declaration - EPD9AKK108469A1857
9AKK108468A1892
Environmental
Environmental Information9AKK108467A6707
REACH Declaration9AKK108466A1425
RoHS Information9AKK108466A1424
RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP825ef000-86ef-4390-b3bc-469b4df74414 Italy (IT)
Simplified SCIPd099b132-2ee3-4495-9251-a4214d0153e2 Germany (DE)
cb69cc10-63ba-41bc-bda5-6e03afef0b0c France (FR)
40eb3dde-d3b2-406a-84b2-4e1f63035e08 Spain (ES)
34a4dc9f-1eec-432d-bc69-a23d9b967e02 Netherlands (NL)
7f78b6a1-9f5e-437f-bf87-938e43fbc68c Poland (PL)
7d306bbd-549c-4034-bcdc-f032dbe79dad Norway (NO)
94c56379-8fca-4a40-90da-227859ef3b3a Finland (FI)
467ed015-eaf9-4cfa-9c3c-9fbb93438f8a Sweden (SE)
8449ca87-1e19-4f50-9bdb-a73a181dbfb5 Germany (DE)
efb9a579-3068-4246-ade0-55e6c2d93a1d Germany (DE)
1311aed6-b2fb-436a-94b9-58f9aabe78bc France (FR)
8a7e9128-6d32-46a7-a085-4c8ad467a9da Netherlands (NL)
435ee1cf-a647-4d14-917f-a92c18664a63 Netherlands (NL)
06d32ce4-2192-4b66-b435-1b8a3dffcde2 Germany (DE)
a75d22c6-706c-4b95-a7c7-17d7a6b8ea5f Denmark (DK)
9fa63426-af62-4435-aeb2-89f997a7bc0d Germany (DE)
41ae1071-0864-43fe-9d1a-e4fee3be8061 Croatia (HR)
51202b64-a5f6-4add-b57d-ea00954dc5e4 Czech Republic (CZ)
34501fec-5f8a-40b3-83a7-964289f7d735 Poland (PL)
297c4a69-cd7e-4b69-b7ee-2d691192115e Netherlands (NL)
d57b5d6d-2a78-44ba-8573-d248d355190e Netherlands (NL)
436a73af-7a7d-4e9e-ada8-2355988c26b0 Estonia (EE)
6afcc577-c53f-43c1-9b38-3e1bdb07daf4 Greece (GR)
c32813d1-7891-418b-8719-4944cb65073a Portugal (PT)
7f5fce92-caf0-4896-b0c7-ac8ce1387064 Bulgaria (BG)
c55d0677-9be7-446d-96e9-b3a3d55d77ea Sweden (SE)
cf43b9fd-9c06-4093-b7e0-3c1c15e5b763 Poland (PL)
Ordering
Order Code US and CanadaXT4NE4250BFF000XXX
EAN8015644695927
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width140 mm
Product Net Height160 mm
Product Net Depth / Length82.5 mm
Product Net Weight2.872 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width151 mm
Package Level 1 Height214 mm
Package Level 1 Depth / Length171 mm
Package Level 1 Gross Weight3.023 kg
Package Level 1 EAN8015644695927
Additional Information
Circuit Breaker Type to be AssociatedPower Distribution
Connecting Capacity Main CircuitBusbar 85..200 mm²
Current TypeAC/DC
Electrical Durability120 cycles per hour
8000 cycle
Mechanical Durability240 cycles per hour
25000 cycle
Number of Poles4
Opening TimeCB with SOR 15 ms
CB with UVR 15 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 16.44 W
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
Rated Current (In)250 A
Rated Frequency (f)50 / 60 Hz
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)1250…2500 A
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 20 kA
(690 V AC) 10 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 20 kA
(690 V AC) 10 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)250 A
Recommended Screw DriverMain Circuit M8
ReleaseTMA
Release TypeTM
Setting Range175...250 A
Short-Circuit Performance LevelN
StandardsIEC60947-2
Sub-typeXT4
Terminal Connection TypeFront
Terminal TypeBolt
Tightening Torque8 N·m
VersionF
CAD Dimensional Drawing1SDH001295R0677
Certificates and Declarations
ATEX CertificateNo certification needed
Data Sheet, Technical Information1SDC210100D0206
1SDC210099D0206
Declaration of Conformity - CE9AKK106713A5529
GL Certificate1SDL000163R0095
LR Certificate1SDL000163R0100
UL CertificateNo certification needed
VDE CertificateNo certification needed
Dimension Diagram1SDH000722R0100
Mechanical Drawings1SDH000722R0100
Wiring Diagram1SDM000068R0001
Instructions and Manuals1SDH000722R0001
Classifications
ETIM 7EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
UNSPSC39120000
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.