ABB 1SDA060222R1 1SDA060222R1 ABB T6N 800 TMA 800-8000 4p F F InN 100%In View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA060222R1 ABB T6N 800 TMA 800-8000 4p F F InN 100%In

1SDA060222R1

060222

ABB

1 Pcs.

T6N 800 TMA 800-8000 4p F F InN=100%In T6N800 TMA R800 4P F F

Automation > Power circuit-breaker for trafo/generator/installation protection
T6

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Circular Value
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental
Environmental Information9AKK10103A1058
9AKK108467A6707
REACH Declaration9AKK108466A1425
RoHS Information9AKK108466A1424
RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Ordering
EAN8015644626822
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width280 mm
Product Net Height268 mm
Product Net Depth / Length103.5 mm
Product Net Weight12 kg
Container Information
Package Level 1 Units1 piece
Package Level 1 Width305 mm
Package Level 1 Height285 mm
Package Level 1 Depth / Length370 mm
Package Level 1 Gross Weight14 kg
Package Level 1 EAN8015644626822
Additional Information
Electrical Durability5000 cycle
60 cycles per hour
Mechanical Durability20000 cycle
120 cycles per hour
Number of Poles4
Power Lossat Rated Operating Conditions per Pole 31 W
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
Rated Current (In)800 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 70 kA
(230 V AC) 70 kA
(380 V AC) 36 kA
(400 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 30 kA
(500 V AC) 25 kA
(690 V AC) 15 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 70 kA
(230 V AC) 70 kA
(380 V AC) 36 kA
(400 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 30 kA
(500 V AC) 25 kA
(690 V AC) 20 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 2 Poles in Series 25 kA
(750 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)800 A
ReleaseTMA
Release TypeTM
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeT6
Suitable ForT6
Suitable for Product ClassMoulded Case Circuit Breakers
Terminal Connection TypeFixed Circuit-Breakers
Front
Test Voltage Max (Utest)3500 V
VersionF
Certificates and Declarations
Data Sheet, Technical Information1SDC210015D0201
Declaration of Conformity - CE9AKK106713A5538
GL Certificate1SDL000163R0057
Instructions and Manuals1SDH000511R0001
Classifications
ETIM 7EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
UNSPSC39121100
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.