View larger
1SDA070959R1
070959
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | dbba8de8-e106-464e-9f7a-70e1c52d73e8 Italy |
| Simplified SCIP | 178cd5e4-90e6-4756-aa08-fc2ca7f9cbdf Germany |
| 07b2ee6d-9669-48f2-81cb-7096d374a22f Finland | |
| e2ad3f74-e732-49ae-924f-de25de5667ce Greece | |
| 913a7bdc-abb0-4868-b764-e2c4478df87e Poland | |
| c78e0d7b-9b07-4a76-b11f-90394d04a8b0 Poland | |
| 50f75dab-6e56-4334-a09d-f71f465f8d84 Portugal | |
| e7db332f-d8d9-4961-8d2b-f868098c88a1 Sweden | |
| 40d8706c-b2ff-4906-aed2-3b2c6342d505 Hungary | |
| de42216d-1174-4e90-850b-187aa7e153ad Belgium | |
| d975d8fe-3465-4b4a-90c4-36eb53195c74 Spain | |
| 5cff99fb-8282-4cc3-85e7-7c2e12077868 Bulgaria | |
| 7d0796b3-23d2-4227-8367-4ed5dc9049b7 France | |
| 1323d27d-b94a-4844-819a-6a0fc4241ad6 Croatia | |
| 4f4a91d6-cf17-48a1-8d11-1b767d85d409 Hungary | |
| 81cb16d3-b575-498a-8950-e58a1d30f17f Norway | |
| c4b9fbbe-b1a1-4005-8a2e-2a2e0fbc60a2 Poland | |
| 5863bdce-65f0-46ab-bbe3-a55ee310aa03 Czech Republic | |
| faba19e6-285a-4f36-b3ca-ec5ca0de5b98 Denmark | |
| 97279c38-73bf-46c4-b7a3-c4e760f6e2a7 Estonia | |
| 3b415c89-d3cb-421c-ad9f-2d086c97adb0 Germany | |
| 3fb1a001-1405-4954-8413-cab41f6633fc Germany | |
| 6c3497ce-0d18-41a5-a99e-17673c3900a2 Germany | |
| 1ef18321-c03c-4252-8bc2-dd7541c07d92 Germany | |
| 1ea37df1-ebc2-4bb3-9b49-40f9749c09d0 Belgium | |
| f100e551-2c6f-496a-89d5-eba4656323da Sweden | |
| c4572356-6e9b-468e-8684-27ead26e969c Netherlands | |
| 64c37c6a-d24b-4dd1-8836-2ff6d99bb685 France | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z2NREHBK200A000000XX |
| EAN | 8015644748098 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 276 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 41 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 515 mm |
| Package Level 1 Gross Weight | 46 kg |
| Package Level 1 EAN | 8015644748098 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0083 |
| Technical | |
| Connecting Capacity | 1200 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 15000 cycle |
| Ue = 500 ... 690 V 15000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 83 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 66 kA |
| (230 V AC) 66 kA | |
| (380 V AC) 66 kA | |
| (400 V AC) 66 kA | |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 66 kA | |
| (660 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 66 kA |
| for 3 s 50 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 66 kA | |
| (525 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001000R0100 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1250 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 66 kA |
| Overload release current setting (EF002336) | 1250 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 12500 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1875.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |