View larger
1SDA071423R1
071423
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 72452faf-7c65-4b20-b5ef-02173113738c India |
| Simplified SCIP | 2db60012-c364-4efb-8782-65e0dfb5ea1a Portugal |
| e9060421-3385-4a2d-8323-e76a97b02c99 France | |
| 883588ac-dff6-4f31-a5f4-8818d5a68139 Germany | |
| 32529082-9f94-4a53-b3e6-7bfeb27c7a8d Sweden | |
| 122f6d42-da03-4608-98e0-f160f239d82c Germany | |
| 4c719059-5468-46b2-b931-091c4d8ec6b6 France | |
| 17a2e5b6-3e18-44df-86f5-a3d02b4422df Poland | |
| 249e3dbe-7a1e-4790-a847-cddb139d342f Sweden | |
| 4efd399c-6ac2-46d3-8fca-87e82094e1ea Bulgaria | |
| 5f61c683-ce24-40a1-afef-868ae85ffed5 Greece | |
| 0fd957ea-f0f3-4e40-a2ff-6bd9cd3e7ff7 Norway | |
| 20997164-0722-4498-b27c-0f79e0b59010 Belgium | |
| bafc1c9a-163e-4a91-bbad-577e92a75840 Croatia | |
| de0a8552-05cf-48c4-a95f-a241c3112a2e Denmark | |
| 8e925362-5096-4da3-9d85-ab015c43e515 Finland | |
| 96fe8542-2a63-4236-afcd-7fd6b87bc2d8 Germany | |
| c52146bd-25f2-4b48-93c0-b9c9ee27e20a Germany | |
| 2308dfc6-a24a-4f00-b35a-34db52e5fcc2 Poland | |
| 11d19788-7d6b-43ff-bf7b-837f37491ae3 Poland | |
| 56344a3d-71fe-4d88-a762-f29ccc1c52e3 Germany | |
| 06fecd14-b34f-4e63-8c9d-941aa760eb2a Hungary | |
| a814d7ab-f8a3-451c-a059-81d8178dc864 Netherlands | |
| 8fefa987-a751-4aa0-9241-55b7d132d4d5 Czech Republic | |
| 13b6fdc9-ec1a-452a-8ad9-41f379cfedea Hungary | |
| 41ce8fdc-aded-4f43-84e4-f3f6b10ae1e3 Estonia | |
| a73edc8a-635a-43bb-b16c-5dbbc921f2fa Belgium | |
| d1e4ee02-ad36-45cd-9044-51c4633f42f7 Spain | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZACQEGBC000A000000XX |
| EAN | 8015644752736 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644752736 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0042 |
| Technical | |
| Connecting Capacity | 1000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 78 W |
| Rated Current (In) | 1000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 50 kA |
| Overload release current setting (EF002336) | 1000 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 10000 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1500.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |