View larger
1SDA071372R1
071372
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | f07eacfc-206c-4b4e-babd-f7a397686868 China |
| Simplified SCIP | 4c6d8e5f-bdb5-4e4c-8a58-8cab026cdc23 Sweden |
| b22b6b91-90b2-4e20-ba0b-ba2eeb04e85e Croatia | |
| 7ad64e79-e5af-428e-a810-fd01a36f1b8c Greece | |
| b3345880-63b1-4e42-9d57-c3cb7833a381 Hungary | |
| 7eceb029-8344-4992-bcfc-a2c60b393274 Germany | |
| 728e5c4c-05ca-49d3-bc1b-d88486679bbe Belgium | |
| 8e6df8b0-26a0-4895-add6-b7346071eedf Spain | |
| 5b8d7468-caa1-4cd3-8f65-5d6ed57ec765 France | |
| 66310089-2af1-4795-85f3-4062ae4dc256 Poland | |
| 5023b79f-2555-4581-8fce-ab4dc959d2f6 Germany | |
| 6dfb148a-3c56-4f97-b132-8fbf06632e66 Hungary | |
| d33779a3-d9b3-45a6-b50c-345ccd9d3a3e Norway | |
| 7658760c-d7b3-4019-871a-88ad190c6ecb Estonia | |
| e02a8178-27c0-42a7-b56a-fa3a5f03de9e Poland | |
| c6ceae03-5ccb-4246-8080-a71832481862 Sweden | |
| 04510052-9592-4a56-bdfc-ad8b29572b28 Portugal | |
| 87265bb8-087c-4fe2-a3ba-6a9404ddebb6 Bulgaria | |
| 5ad89dec-26cb-41e6-9822-dc4470781ef8 Belgium | |
| c3391abe-bd59-4159-9ea4-24c866ab6976 Czech Republic | |
| ba72005c-c8ba-458b-839f-df67c14c49fb Germany | |
| 34c2414a-9cff-4af4-8744-e718d846c9cc Poland | |
| 3740c6d9-5a04-49f7-b736-8afd3737c25e Netherlands | |
| 532bb0d3-1e27-4579-ba42-61128bda6b1c Finland | |
| e94f19a4-998d-4bf5-b4ad-249607b5a631 Germany | |
| 853c482b-3b5c-4543-806a-90fcafab76b3 Denmark | |
| bf5f933a-5a7e-45b6-9165-d1d06b3bb6ba Germany | |
| 302b6729-5f11-4cf5-b68a-37d707475ba3 France | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZABPEFBB000A000000XX |
| EAN | 8015644752224 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644752224 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0042 |
| Technical | |
| Connecting Capacity | 500 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 50 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA |
| (230 V AC) 42 kA | |
| (380 V AC) 42 kA | |
| (400 V AC) 42 kA | |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |