View larger
1SDA071453R1
071453
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 66ca81a5-53b8-42ea-a79a-95d434d4b86f India |
| Simplified SCIP | 26a8cbc9-c988-429e-a240-a6d0b8c95b75 Norway |
| a87db375-390d-449b-9b74-ea6ff52ee643 Finland | |
| dcc0cd22-7a73-49d2-ac71-eeeadb5f929d Germany | |
| 3285b0ae-4da1-4bb1-87ed-05cd2185ba9c Hungary | |
| f4f41197-6b27-442a-b9bd-6b2acaa808bd Poland | |
| 4983b1e2-9454-4743-83de-9a8ad9192461 Czech Republic | |
| a1984f4d-abe2-4d54-9066-b1b324b8c9e5 Hungary | |
| 7961c857-20f4-4cff-a096-d6ba2800a7ce Netherlands | |
| 0c16ee13-76b5-41f4-93ec-2ff82ac7e5f4 Belgium | |
| cd8d9b23-ce84-4704-81b6-146fd61e8e66 Spain | |
| 3c0c987e-7a27-4d68-98d6-3a3fc71424ce Estonia | |
| c86d62e5-e4a3-453e-8852-ba24a368f1ae Portugal | |
| df3dfd0e-b318-485c-91e2-dfb49e476091 France | |
| 93819e64-8422-4dd9-89b6-40e76536ecd3 Germany | |
| c69b2604-f48f-4b10-97d2-3cf37f02d6a0 Sweden | |
| cb38b194-1c4f-4ec0-b7d3-74453a89df6f France | |
| 3ac1f301-723a-48b5-a130-89c01095c3a0 Germany | |
| 39cbb25d-91b3-4454-8fdc-13cba9e9871e Greece | |
| e0c69b94-690e-485f-a3db-af0f32295c96 Poland | |
| 62ee6b71-8e59-422b-8eba-d9607ce9ea53 Sweden | |
| c4fee19a-7007-4ba6-aa3f-a0d6469db965 Bulgaria | |
| ca44e956-ef55-407c-b4bd-7f047d4491f3 Croatia | |
| d10ea5ff-fb2a-4917-a168-661857be726f Denmark | |
| 698acbb4-d49d-4ef0-a01c-568eaff34e37 Germany | |
| d01953c3-5270-4182-8e55-19cb9a2e3401 Germany | |
| 262b32c6-c87c-4146-8063-37739e159c18 Belgium | |
| e04eb596-37c0-4478-98c2-66becfd82cdb Poland | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZABREHBC000A000000XX |
| EAN | 8015644753030 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644753030 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0042 |
| Technical | |
| Connecting Capacity | 1000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 6500 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 122 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA |
| (230 V AC) 42 kA | |
| (380 V AC) 42 kA | |
| (400 V AC) 42 kA | |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |