View larger
1SBL276060R2100
276060
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100220C0201 |
| Instructions and Manuals | 1SBC101035M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 86 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.36 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 50 A |
| (690 V) 60 °C 42 A | |
| (690 V) 70 °C 37 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 32 A |
| (440 V) 60 °C 32 A | |
| (500 V) 60 °C 28 A | |
| (690 V) 60 °C 21 A | |
| (380 / 400 V) 60 °C 32 A | |
| (220 / 230 / 240 V) 60 °C 33 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 32 A |
| (440 V) 60 °C 32 A | |
| (500 V) 60 °C 28 A | |
| (690 V) 60 °C 21 A | |
| (380 / 400 V) 60 °C 32 A | |
| (220 / 230 / 240 V) 60 °C 33 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 50 A | |
| (220 V) 3 Poles in Series, 60 °C 42 A | |
| (220 V) 3 Poles in Series, 70 °C 37 A | |
| (72 V) 1-Pole, 40 °C 50 A | |
| (72 V) 1-Pole, 60 °C 42 A | |
| (72 V) 1-Pole, 70 °C 37 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 50 A | |
| (220 V) 3 Poles in Series, 60 °C 42 A | |
| (220 V) 3 Poles in Series, 70 °C 37 A | |
| (72 V) 1-Pole, 40 °C 50 A | |
| (72 V) 1-Pole, 60 °C 42 A | |
| (72 V) 1-Pole, 70 °C 37 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 25 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 25 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Power AC-3 (Pe) | (415 V) 15 kW |
| (440 V) 18.5 kW | |
| (500 V) 18.5 kW | |
| (690 V) 18.5 kW | |
| (380 / 400 V) 15 kW | |
| (220 / 230 / 240 V) 9 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 15 kW |
| (440 V) 18.5 kW | |
| (500 V) 18.5 kW | |
| (690 V) 18.5 kW | |
| (380 / 400 V) 15 kW | |
| (220 / 230 / 240 V) 9 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-2 / AC-4) 150 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V |
| 60 Hz 24 ... 60 V | |
| DC Operation 20 ... 60 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2.4 W |
| at Rated Operating Conditions AC-3 per Pole 0.9 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Tightening Torque | Control Circuit 1.2 N·m |
| Main Circuit 2.5 N·m | |
| Terminal Type | Ring-Tongue Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 50 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 2 hp |
| (200 ... 208 V AC) Three Phase 10 hp | |
| (220 ... 240 V AC) Three Phase 10 hp | |
| (240 V AC) Single Phase 5 hp | |
| (440 ... 480 V AC) Three Phase 20 hp | |
| (550 ... 600 V AC) Three Phase 25 hp | |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| Main Circuit 22 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 24 A |
| (200 ... 208 V AC) Three Phase 32.2 A | |
| (220 ... 240 V AC) Three Phase 28 A | |
| (240 V AC) Single Phase 28 A | |
| (440 ... 480 V AC) Three Phase 27 A | |
| (550 ... 600 V AC) Three Phase 27 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 5a0fff11-619b-4f42-9724-15c1084b659f China |
| Simplified SCIP | 18339980-6a85-473c-83f8-4767e2e3c4da Portugal |
| 1cb5ad1e-f4e0-4019-a7bb-8afdd559e912 Belgium | |
| 27b47577-756b-49fc-bae5-3fd0d5b76bae Sweden | |
| 53e99cf1-0134-41fe-afda-123e1f4f317e Denmark | |
| 5ff2a297-a835-4a4f-a4bc-d21b033d1d9c Spain | |
| 69e3521e-03ce-4e8e-809c-11fd4692356f Croatia | |
| 6a2c4d09-dc22-407a-be0a-f36ca3f6fe66 Norway | |
| 7270487a-07be-4a02-b8cd-6d83c9191414 Estonia | |
| 9a1d85db-5195-440b-99d0-499cd4275465 France | |
| 9a63f90b-71c6-4e45-b82e-7c6a71a4dcd1 Greece | |
| a4b16947-4287-4234-ac0e-e4a78e9099cc Poland | |
| aedb15da-5d46-4d0a-aac6-b4cd5d9385c4 Netherlands | |
| de142d26-ba0d-4907-bb4a-854dc1b485d2 Bulgaria | |
| e87e23f1-dbdd-4828-b172-76e0ef4b266e Finland | |
| ec969d6d-9787-491b-a994-4d6c3fc2f2c6 Hungary | |
| ecef143a-383f-47c2-9f55-b5e635fe42c8 Germany | |
| fc271630-cce7-402d-99f5-f6758977c861 Czech Republic | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E4000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 94.3 % |
| Certificates and Declarations | |
| CB Certificate | CB_SE-116364 |
| CCC Certificate | CCC_2024010304656668 |
| CQC Certificate | CQC2010010304445623 |
| Declaration of Conformity - CCC | 2020980304001254 |
| Declaration of Conformity - CE | 1SBD250004U1000 |
| Declaration of Conformity - UKCA | 1SBD250035U1000 |
| UL Listing Card | UL_E312527 |
| UR Certificate | UL_20121122-E312527_9_5 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 87 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.36 kg |
| Package Level 1 EAN | 3471523128811 |
| Package Level 2 Units | box 21 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 16.2 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |