ABB 1SDA100205R1 1SDA100205R1 ABB XT4S 250 Ekip Dip LSI In 250A 3p F F View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA100205R1 ABB XT4S 250 Ekip Dip LSI In 250A 3p F F

1SDA100205R1

1SDA100205R1

ABB

1 Pcs.

XT4S 250 Ekip Dip LSI In=250A 3p F F

Automation > Shunt release (for power circuit breaker)
Molded Case Circuit Breakers ≤ 250 A Xtmax

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ABB EcoSolutions
Environmental Product Declaration - EPD9AKK108469A1858
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 56.30 %
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Information9AKK108466A1424
RoHS StatementFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Order
Ean8056221002592
Minimum order quantity1 piece(s)
Customs tariff code85362090
dimensions
Product width105 mm
Product height160 mm
Product depth82.5 mm
Product Net Weight2.5 kg
Packaging information
Packaging Unit Level 1Box 1 piece(s)
Packaging width level 1145 mm
Packaging height level 1210 mm
Packaging depth level 1168 mm
Gross Packaging Weight Level 12.5 kg
EAN packaging level 18056221002592
Additional information
Type of switch to pairPower Distribution
Main Product TypeSACE Tmax XT
Product nameMoulded Case Circuit Breaker
Product typeAutomatic Circuit Breaker
versionF
CAD Dimensional Drawing1SDH002230A1003
Technical data
Current TypeAc
Electrical life120 cycles per hour
8000 cycle(s)
Mechanical durability240 cycles per hour
25000 cycle(s)
Number of poles3P
Opening durationCB with SOR 30 ms
CB with UVR 30 ms
Power lossa Nominal Operating Conditions per Pole 16.40 W
Rated current (IN)250 A
Rated Frequency (f)50/60 Hz
Impulse sealing voltage (UImp)8 kV
Rated insulation voltage (Uthe)1000 V AC
Rated operating voltage690 V AC
Rated service short-circuit power (ICs)(220 V AC) 85 kA
(230 V AC) 85 kA
(240 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 36 kA
(525 V AC) 25 kA
(690 V AC) 12 kA
Nominal extreme short circuit power (ICu)(220 V AC) 85 kA
(230 V AC) 85 kA
(240 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 36 kA
(525 V AC) 25 kA
(690 V AC) 12 kA
Uninterrupted current rating (Iu)250 A
Rated voltage (UR)690 V AC
UncouplingEkip Dip LSI
Release typeEL
Short-circuit performance levelS
Reference standardsIec
SubtypeXT4
UL/CSA Technical Department
Interrupting Rating acc. to UL489(240 V AC) 150 A
(480 V AC) 65 A
(600 V AC) 25 A
Certificates and declarations (document number)
ATEX certifiedNo certification needed
Sheet1SDC210100D0206
1SDC210099D0206
Declaration of Conformity - CE9AKK106713A5529
VDE CertificateNo certification needed
Mechanical drawings1SDH000722R0100
Wiring diagram1SDM000068R0001
Instructions and manuals1SDH000722R0001
1SDH000721R0510
External classifications and standards
ETIM 9EC001023 - Shunt release (for power circuit breaker)
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
Item Classification CodeQ
WEEE Category5. Small equipment (no external size greater than 50cm)

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.